2018-09-05 15:44:12CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND
 NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
 PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE3901.7 (NOT
 PROVIDED)
 3. PROVIDE FULL FLOOR PLAN SHOWING ALL SMOKE/CO ALARMS
 IN EACH LOCATION REQUIRED PER CODE. SHOW ON PLAN ALL
 EXISTING ALARMS. IF NONE ARE EXISTING OR NOT TO CODE,
 SHOW AS NEW INSTALLATIONS. ADDITIONALLY, NEW BEDROOMS
 DO NOT SHOW THE REQUIRED SMOKE ALARM. PROVIDE
 CORRECTION. SMOKE ALARMS MUST BE AT LEAST 3 FEET FROM
 CEILING FAN OR MECHANICAL REGISTER. NFPA 72; 29.8.3.6
 AND 7; FBC R314.3, FBC 107.2.1 (NOT PROVIDED.
 ADDITIONALLY, A CARBON MONOXIDE ALARM IS REQUIRED
 WITHIN 10 FEET OF EACH SLEEPING ROOM, WHICH IS NOT
 CURRENTLY SHOWN.)
 4. CORRECTED.
 5. CORRECTED.
 6. A NOTE ON MECHANICAL SHEET STATES THAT THE
 CONTRACTOR MAY INSTALL A MINI-SPLIT SYSTEM IN LIEU OF
 EXTENDING THE EXISTING A/C SYSTEM. IF THIS IS THE CASE,
 IT APPEARS THAT THE CURRENT ELECTRICAL SYSTEM WOULD BE
 OVERLOADED, BASED ON THE LOAD CALCULATION PROVIDED.
 PROVIDE CLARIFICATION WHICH METHOD WILL BE USED. FBC
 107.2.1 (NOT PROVIDED)
  
 NEW COMMENT:
  
 7. PLAN SHOWS AN EXTERIOR GFCI ON THE SIDE OF THE HOUSE
 ON CIRCUIT 19A, WHICH IS THE SAME CIRCUIT USED FOR
 BATHROOM. THIS IS SHOWN AS A 15 AMP CIRCUIT. A MINIMUM
 OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO
 SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS
 SHALL HAVE NO OTHER OUTLETS. PROVIDE CORRECTION. NEC
 210.11(C)(3) , FBC RE E3703.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER