2017-12-05 08:37:43 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR |
| PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM |
| BONDING TERMINATION POINT. NEC 215.5, 230, 250.50, |
| 250.94, 408.30 FBC RE3706.1, RE3608.1, RE3609.3; FBC |
| 107.2.1 |
| 2. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A |
| TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST |
| ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND |
| NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE |
| INSTALLED AT THE FRONT AND BACK OF THE DWELLING. |
| PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE3901.7 |
| 3. PROVIDE FULL FLOOR PLAN SHOWING ALL SMOKE/CO ALARMS |
| IN EACH LOCATION REQUIRED PER CODE. SHOW ON PLAN ALL |
| EXISTING ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, |
| SHOW AS NEW INSTALLATIONS. ADDITIONALLY, NEW BEDROOMS |
| DO NOT SHOW THE REQUIRED SMOKE ALARM. PROVIDE |
| CORRECTION. SMOKE ALARMS MUST BE AT LEAST 3 FEET FROM |
| CEILING FAN OR MECHANICAL REGISTER. NFPA 72; 29.8.3.6 |
| AND 7; FBC R314.3, FBC 107.2.1 |
| 4. PROVIDE CORRECTION OF NOTE FOR AFCI PROTECTION. |
| CURRENT NOTE STATES PER 2010 NEC (WHICH DOESN'T EXIST) |
| THAT THE RECEPTACLES SHALL BE PROTECTED, BUT CODE |
| STATES: "ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE |
| BRANCH CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT |
| FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, |
| LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, |
| CLOSETS, HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL |
| HAVE AFCI PROTECTION." PROVIDE CORRECTIONS. NEC 210.12; |
| FBC RE3902.12 |
| 5. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| FBC EC R404.1 |
| 6. A NOTE ON MECHANICAL SHEET STATES THAT THE |
| CONTRACTOR MAY INSTALL A MINI-SPLIT SYSTEM IN LIEU OF |
| EXTENDING THE EXISTING A/C SYSTEM. IF THIS IS THE CASE, |
| IT APPEARS THAT THE CURRENT ELECTRICAL SYSTEM WOULD BE |
| OVERLOADED, BASED ON THE LOAD CALCULATION PROVIDED. |
| PROVIDE CLARIFICATION WHICH METHOD WILL BE USED. FBC |
| 107.2.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |