Plan Review Notes
Plan Review Notes For Permit 17110286
Permit Number 17110286
Review Stop E
Sequence Number 1
Notes
Date Text
2017-12-05 08:37:43CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR
 PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM
 BONDING TERMINATION POINT. NEC 215.5, 230, 250.50,
 250.94, 408.30 FBC RE3706.1, RE3608.1, RE3609.3; FBC
 107.2.1
 2. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND
 NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
 PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE3901.7
 3. PROVIDE FULL FLOOR PLAN SHOWING ALL SMOKE/CO ALARMS
 IN EACH LOCATION REQUIRED PER CODE. SHOW ON PLAN ALL
 EXISTING ALARMS. IF NONE ARE EXISTING OR NOT TO CODE,
 SHOW AS NEW INSTALLATIONS. ADDITIONALLY, NEW BEDROOMS
 DO NOT SHOW THE REQUIRED SMOKE ALARM. PROVIDE
 CORRECTION. SMOKE ALARMS MUST BE AT LEAST 3 FEET FROM
 CEILING FAN OR MECHANICAL REGISTER. NFPA 72; 29.8.3.6
 AND 7; FBC R314.3, FBC 107.2.1
 4. PROVIDE CORRECTION OF NOTE FOR AFCI PROTECTION.
 CURRENT NOTE STATES PER 2010 NEC (WHICH DOESN'T EXIST)
 THAT THE RECEPTACLES SHALL BE PROTECTED, BUT CODE
 STATES: "ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE
 BRANCH CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT
 FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS,
 LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS,
 CLOSETS, HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL
 HAVE AFCI PROTECTION." PROVIDE CORRECTIONS. NEC 210.12;
 FBC RE3902.12
 5. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 6. A NOTE ON MECHANICAL SHEET STATES THAT THE
 CONTRACTOR MAY INSTALL A MINI-SPLIT SYSTEM IN LIEU OF
 EXTENDING THE EXISTING A/C SYSTEM. IF THIS IS THE CASE,
 IT APPEARS THAT THE CURRENT ELECTRICAL SYSTEM WOULD BE
 OVERLOADED, BASED ON THE LOAD CALCULATION PROVIDED.
 PROVIDE CLARIFICATION WHICH METHOD WILL BE USED. FBC
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER