2017-12-06 18:31:12 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS. |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT. |
| BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF |
| THE UNIFIED LAND DEVELOPMENT CODE. |
| NOTE: THIS MAY BE DONE LATER WHEN ALL THE TRADES ARE |
| APPROVED AND THE PERMIT IS READY FOR ISSUANCE. |
| |
| 2- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED |
| BY SEC. R101.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014). |
| |
| 3- ARCHITECT TO PROVIDE PARTIAL PLAN SHOWING THE ROOMS |
| ADJACENT TO THE PROPOSED ADDITION AND SHOW COMPLIANCE |
| WITH THE BEDROOM EGRESS REQUIREMENTS OF SEC. 704 |
| FBC-EXISTING BUILDING, 5TH EDITION (2014). CLEARLY |
| IDENTIFY EACH ROOM ON THE FLOOR PLAN. |
| NOTE: BASED ON CITY RECORDS, IT LOOKS LIKE THERE MAY BE |
| NO EGRESS WINDOWS FOR EXISTING BEDROOM LOCATED ON THE |
| NORTH EAST CORNER. |
| |
| 4- PROPOSED WINDOWS FOR NEW BEDROOMS #1 AND #2 DON'T |
| SEEM TO COMPLY WITH THE EGRESS REQUIREMENTS OF SEC. |
| R310.1.2 FBC-RESIDENTIAL. IT LOOKS LIKE THE PROPOSED |
| WINDOW DON'T HAVE THE 24" CLEAR HEIGHT. REVISE AS |
| REQUIRED SHOWING COMPLIANCE AND PROVIDE MANUFACTURER'S |
| SPECS SHOWING THE MIN. CLEAR DIMENSIONS. |
| |
| 5- SPECIFY ATTIC ACCESS LOCATION AND SIZE FOR THE |
| PROPOSED ADDITION AS REQUIRED BY SEC. R807 |
| FBC-RESIDENTIAL. |
| |
| 6- WALL SECTION ON SHEET A.4: SPECIFY SIZE AND SPACING |
| OF ROOF VENTILATION AS REQUIRED BY SEC. R806 |
| FBC-RESIDENTIAL. |
| |
| 7- SHEET A.3: |
| A) WIND NOTE #5 ON THE TOP MIDDLE OF DRAWING SPECIFIES |
| BUILDING EXPOSURE "B". ACCORDING TO SEC. R301.2.1.4 |
| FBC-RESIDENTIAL, THIS BUILDING IS LOCATED IN EXPOSURE |
| "C" NOT "B". REVISE AS REQUIRED. |
| |
| B) ROOF SHEATHING NOTE ON THE MECHANICAL FASTENER |
| SCHEDULE SPECIFIES 8D RING SHANK NAILS AND 10D COMMON |
| NAILS. SEC. R803.2.3.1 REQUIRES MIN. 8D RING SHANK |
| NAILS. PROVIDE ENGINEERING ANALYSIS SHOWING THAT THE |
| ALTERNATE ROOF SHEATHING SPECIFICATIONS USING 10D NAILS |
| AT SPECIFIED SPACING ARE EQUAL OR BETTER THAT THE ROOF |
| SHEATHING NAILING PATTERN USING 8D RING SHANK NAILS OR |
| REMOVE ALTERNATE NAILING PATTERN. |
| |
| 8- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW. |
| VALUE TO INCLUDE ALL THE LABOR, MATERIALS AND |
| CONTRACTOR'S OVERHEAD AND PROFIT (EVEN FOR |
| OWNER/BUILDERS) AND ALL DESIGN PROFESSIONAL FEES AS |
| REQUIRED BY SEC. 109.3 CITY AMENDMENTS. VALUATION WAS |
| UPDATED TO +/- $70,000. THE PERMIT FEE BALANCE IS |
| $1843.51. |
| |
| 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.001 FOR: |
| A) ALL WINDOWS AS SPECIFIED ON PLANS. |
| |
| B) EXTERIOR DOOR AS SPECIFIED ON PLANS. |
| |
| C) ROOF SHINGLES AS SPECIFIED ON PLANS. |
| |
| D) WINDOW MULLIONS AS SHOWN ON PLANS. NOTE: CLEARLY |
| SPECIFY AND MARK MULLION SIZE TO BE INSTALLED TO VERIFY |
| COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES. |
| |
| E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| PLANS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER |
| PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR |
| ARCHITECT TO LIST THE FLORIDA PRODUCT APPROVAL NEXT TO |
| EACH SPECIFIED CONNECTOR. |
| |
| F) HURRICANE SHUTTERS IF WINDOWS AND DOORS WITH GLAZING |
| DON'T HAVE IMPACT GLASS. NOTE: AND PROVIDE COMPLETE |
| HURRICANE SHUTTERS INSTALLATION SCHEDULE. SEE CITY |
| SAMPLE. |
| |
| 10- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| FOR REFERENCE TO HELP EXPEDITE THE REVIEW PROCESS. |
| |