Plan Review Notes
Plan Review Notes For Permit 17110229
Permit Number 17110229
Review Stop P
Sequence Number 1
Notes
Date Text
2017-11-08 14:45:1611/8/17 1ST PLUMBING REVIEW**DENIED**
  
 1) PLEASE EXPLAIN IS THIS A LIKE FOR LIKE REPLACEMENT
 AND ARE ANY DRAINS BEING ADDED OR DELETED FROM THE
 EXISTING SYSTEM OR CHANGING OF SIZE OF ANY DRAINS. FBC
 107.2.1
  
 2) PLEASE EXPLAIN HOW YOU PLAN ON LEAK CHECKING IF YOU
 DO NOT PLAN ON ON CUTTING DRYWALL CEILING OPEN FROM
 BELOW AND HOW THE INSPECTOR IS INSPECT WORK HE IS
 UNABLE TO SEE. FPC 312.1- RUNNING TEST OK
  
 3) PROVIDE MANUFACTURE INSTALLATION MANUAL AND ROOF
 DRAIN SPEC (2-COPIES OF EACH)
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  