Plan Review Notes For Permit 17110229 |
Permit Number |
17110229 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-11-08 14:45:16 | 11/8/17 1ST PLUMBING REVIEW**DENIED** | | | | 1) PLEASE EXPLAIN IS THIS A LIKE FOR LIKE REPLACEMENT | | AND ARE ANY DRAINS BEING ADDED OR DELETED FROM THE | | EXISTING SYSTEM OR CHANGING OF SIZE OF ANY DRAINS. FBC | | 107.2.1 | | | | 2) PLEASE EXPLAIN HOW YOU PLAN ON LEAK CHECKING IF YOU | | DO NOT PLAN ON ON CUTTING DRYWALL CEILING OPEN FROM | | BELOW AND HOW THE INSPECTOR IS INSPECT WORK HE IS | | UNABLE TO SEE. FPC 312.1- RUNNING TEST OK | | | | 3) PROVIDE MANUFACTURE INSTALLATION MANUAL AND ROOF | | DRAIN SPEC (2-COPIES OF EACH) | | | | TIM HUNT | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | 561-805-6695 | | [email protected] | | |
|