2019-02-14 13:58:53 | *PROVISO* | | | | PROVIDE THE REQUIERED TEST REPORTS FOR THE SPECIFIC | | CONDITIONS FOR THIS JOB. THIS CAN PERFORMED ON SITE AND | | CERTIFIED BY AN ENGINEER. | | | | | | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. | | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM | | CEILING. PROVIDE A COPY OF THE TEST REPORT. | | | | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED | | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. | | | | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | OR UL 723. | | | | | | . | | | | | | | | |
|