| 7TH REVIEW - THE TEST REPORTS PROVIDED FOR "MASTERS |
| BUILDING PRODUCTS" (STAPLED TO SPEC SHEET FOR |
| "SOUNDGUARD") USED AN ASSEMBLY WITH A DROPPED GYPSUM |
| CEILING. FLAME SPREAD TEST NOT PROVIDED. |
| |
| "QUIET WALK PLUS" SPEC SHEET WAS ALSO PROVIDED; NO TEST |
| REPORTS WERE PROVIDED WITH THE SPEC SHEET. |
| |
| PLEASE SEE PREVIOUS SIX COMMENT LISTS REGARDING THE |
| THREE TEST REPORTS REQUIRED FOR FLOORING UNDERLAYMENT. |
| PLEASE CONTACT ME IF YOU NEED ASSISTANCE. |
| |
| THIS INFORMATION CAN BE SENT VIA EMAIL RATHER THAN |
| RESUBMITTAL; INCLUDE PERMIT NUMBER AND "FLOORING |
| UNDERLAYMENT" IN THE SUBJECT LINE. |
| |
| 2. TILE IS PROPOSED ON 1ST FLOOR, VINYL ON 2ND FLOOR. |
| |
| A. FBC B 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| |
| B. FBC B 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| |
| C. FBC B 720.2, SOUND-INSULATING MATERIALS TO HAVE A |
| FLAME SPREAD INDEX OF NOT MORE THAN 25, SMOKE-DEVELOPED |
| INDEX NOT MORE THAN 450. (NOTE THAT THIS CODE REFERENCE |
| HAS BEEN CORRECTED TO REFLECT COMBUSTIBLE |
| CONSTRUCTION). |
| |
| |
| |
| |