Plan Review Notes
Plan Review Notes For Permit 17110126
Permit Number 17110126
Review Stop B
Sequence Number 7
Notes
Date Text
2019-01-04 07:11:39****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 FROM PREVIOUS LISTS: PLEASE DO NOT RESUBMIT WITHOUT
 THIS INFORMATION!! PLEASE CONTACT ME IF YOU NEED
 ASSISTANCE!!
  
 7TH REVIEW - THE TEST REPORTS PROVIDED FOR "MASTERS
 BUILDING PRODUCTS" (STAPLED TO SPEC SHEET FOR
 "SOUNDGUARD") USED AN ASSEMBLY WITH A DROPPED GYPSUM
 CEILING. FLAME SPREAD TEST NOT PROVIDED.
  
 "QUIET WALK PLUS" SPEC SHEET WAS ALSO PROVIDED; NO TEST
 REPORTS WERE PROVIDED WITH THE SPEC SHEET.
  
 PLEASE SEE PREVIOUS SIX COMMENT LISTS REGARDING THE
 THREE TEST REPORTS REQUIRED FOR FLOORING UNDERLAYMENT.
 PLEASE CONTACT ME IF YOU NEED ASSISTANCE.
  
 THIS INFORMATION CAN BE SENT VIA EMAIL RATHER THAN
 RESUBMITTAL; INCLUDE PERMIT NUMBER AND "FLOORING
 UNDERLAYMENT" IN THE SUBJECT LINE.
  
 2. TILE IS PROPOSED ON 1ST FLOOR, VINYL ON 2ND FLOOR.
  
 A. FBC B 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC B 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC B 720.2, SOUND-INSULATING MATERIALS TO HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 25, SMOKE-DEVELOPED
 INDEX NOT MORE THAN 450. (NOTE THAT THIS CODE REFERENCE
 HAS BEEN CORRECTED TO REFLECT COMBUSTIBLE
 CONSTRUCTION).
  
  
  
  