2018-09-18 11:06:14 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: NEW REVIEW BASED ON DESIGN |
| PROFESSIONAL CHANGE. DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE ACCURATE LOAD CALCULATION TO JUSTIFY SERVICE |
| SIZE. LOAD CALCULATION PROVIDED IS NOT CODE COMPLIANT. |
| NEC 220 |
| 2. BASED ON LOADS PROVIDED, SERVICE IS NOT OF |
| SUFFICIENT SIZE FOR THE LOAD. PROVIDE CORRECTION. NEC |
| 215.2, 215.3, 408.30, 408.36 |
| 3. BASED ON LOADS PROVIDED, FEEDERS TO FPL ARE NOT |
| SIZED PROPERLY. PROVIDE CORRECTION. NEC 310.15(B)(16) |
| 4. PROVIDE CALCULATION FOR WIRE SIZE TO METERS/ METER |
| BANKS. NEC 220, 215.2, 215.3, 240.21 |
| 5. PROVIDE METHOD OF TAPPING WIRES TO EACH METER. AS |
| SHOWN ON PLAN, THE WIRES WOULD GO TO INDIVIDUAL METERS. |
| HOW WOULD THIS BE ACCOMPLISHED? IF A TAP IS TO BE USED, |
| TAP RULES DICTATE THAT THE TAPS MUST TERMINTATE IN A |
| SINGLE BREAKER OR SET OF FUSES. PROVIDE COMPLIANCE. NEC |
| 240.21(B)(5); WPB FBC 107.2.1 |
| 6. SHEET E-1 SHOWS UNIT TYPES A, B, AND C. SHEET E-3 |
| SHOWS UNIT TYPES A AND B. ATTEMPTED LOAD CALCULATION |
| SHOWS 3 TYPES OF UNITS. PROVIDE CLARIFICATION AND/OR |
| CORRECTION. WPB FBC 107.2.1 |
| 7. PROVIDE ACCURATE SIZED GROUNDING ELECTRODE |
| CONDUCTOR. NEC 250.66 |
| 8. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| NEC 110.9, 110.10 |
| 9. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANELS. |
| NEC 110.3, 110.9 |
| 10. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| 11. PROVIDE SPEC SHEET FOR 4000 VA RANGE SPECIFIED IN |
| LOAD CALCULATIONS. NEC 110.3 |
| |
| BE ADVISED THAT THERE SEEMS TO BE A SUBSTANTIAL AMOUNT |
| OF INFORMATION INCORRECT AND/OR MISSING WITH THIS PLAN. |
| FUTURE ADDITIONAL COMMENTS ARE POSSIBLE WHEN THE |
| INFORMATION ABOVE IS SUPPLIED. |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |