Notes
Date Text
2018-09-18 11:06:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: NEW REVIEW BASED ON DESIGN
 PROFESSIONAL CHANGE. DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ACCURATE LOAD CALCULATION TO JUSTIFY SERVICE
 SIZE. LOAD CALCULATION PROVIDED IS NOT CODE COMPLIANT.
 NEC 220
 2. BASED ON LOADS PROVIDED, SERVICE IS NOT OF
 SUFFICIENT SIZE FOR THE LOAD. PROVIDE CORRECTION. NEC
 215.2, 215.3, 408.30, 408.36
 3. BASED ON LOADS PROVIDED, FEEDERS TO FPL ARE NOT
 SIZED PROPERLY. PROVIDE CORRECTION. NEC 310.15(B)(16)
 4. PROVIDE CALCULATION FOR WIRE SIZE TO METERS/ METER
 BANKS. NEC 220, 215.2, 215.3, 240.21
 5. PROVIDE METHOD OF TAPPING WIRES TO EACH METER. AS
 SHOWN ON PLAN, THE WIRES WOULD GO TO INDIVIDUAL METERS.
 HOW WOULD THIS BE ACCOMPLISHED? IF A TAP IS TO BE USED,
 TAP RULES DICTATE THAT THE TAPS MUST TERMINTATE IN A
 SINGLE BREAKER OR SET OF FUSES. PROVIDE COMPLIANCE. NEC
 240.21(B)(5); WPB FBC 107.2.1
 6. SHEET E-1 SHOWS UNIT TYPES A, B, AND C. SHEET E-3
 SHOWS UNIT TYPES A AND B. ATTEMPTED LOAD CALCULATION
 SHOWS 3 TYPES OF UNITS. PROVIDE CLARIFICATION AND/OR
 CORRECTION. WPB FBC 107.2.1
 7. PROVIDE ACCURATE SIZED GROUNDING ELECTRODE
 CONDUCTOR. NEC 250.66
 8. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 9. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANELS.
 NEC 110.3, 110.9
 10. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 11. PROVIDE SPEC SHEET FOR 4000 VA RANGE SPECIFIED IN
 LOAD CALCULATIONS. NEC 110.3
  
 BE ADVISED THAT THERE SEEMS TO BE A SUBSTANTIAL AMOUNT
 OF INFORMATION INCORRECT AND/OR MISSING WITH THIS PLAN.
 FUTURE ADDITIONAL COMMENTS ARE POSSIBLE WHEN THE
 INFORMATION ABOVE IS SUPPLIED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746