Plan Review Notes For Permit 17110126
Permit Number 17110126
Review Stop M
Sequence Number 4
Notes
Date Text
2018-09-18 13:52:123RD REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION,
 EXISTING BUILDING CODES
 PERMIT #17110126
 9/18/18
  
 1) THE REVISED PLAN IS STILL INDICATING A 2" CLEARANCE
 WILL BE PROVIDED AROUND THE AIR HANDLER, HOWEVER 4" IS
 REQUIRED.
  
 2) THE REQUESTED CORRECTED ENERGY COMPLIANCE FORMS WERE
 NOT CORRECTED AND RESUBMITTED.
  
 3) THE AC CALCULATIONS ARE BASING DESIGN CONDITIONS ON
 FT. LAUDERDALE, AND ARE INDICATING TRANE SYSTEMS TO BE
 INSTALLED, HOWEVER RHEEM SYSTEMS ARE SHOWN ON THE PLAN.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  