Plan Review Notes
Plan Review Notes For Permit 17110126
Permit Number 17110126
Review Stop B
Sequence Number 4
Notes
Date Text
2018-05-13 10:15:04****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. A0 INDICATES THE BUILDING TYPE AS IIB. PLEASE ADVISE
 AS TO HOW ENGINEER HAS MADE THIS DETERMINATION. OUR
 RECORDS SHOW TWO RECORDS RESEARCH REQUESTS DONE IN
 2/2017 AND 9/2017, AND THE RECORDS SHOW WOOD FRAME IN
 THIS STRUCTURE. ALSO, THE ROOF PERMIT 98090008 HAS A
 SPECIFICATION FOR A NAILABLE DECK.
  
 THE PREVIOUS REVIEWER RELIED ON THIS INFORMATION WHEN
 DOING THE REVIEW. FOR A COMBUSTIBLE BUILDING, THE FLAME
 SPREAD FOR THE FLOORING UNDERLAYMENT HAS A MORE
 STRINGENT REQUIREMENT OF 25 AS OPPOSED TO 200 FOR TYPE
 I/TYPE II BUILDINGS.
  
 WITHOUT ACCURATE INFORMATION, AN ACCURATE CHECKLIST
 CANNOT BE PROVIDED AT THIS TIME. HAS ENGINEER BEEN TO
 THIS JOB? PROVIDE INFORMATION REGARDING WALL
 CONTRUCTION, FLOOR CONSTRUCTION, ROOF CONSTRUCTION.
  
 2. FLOORING PROPOSED IS NOT CLEAR. PLEASE ADVISE. A
 FLOORING UNDERLAYMENT CANNOT BE REVIEWED UNTIL THE
 FLOOR CONSTRUCTION AND FLOORING PROPOSED IS DETERMINED.
  
 PLEASE NOTE THAT VERY FEW PRODUCTS HAVE THE THREE TESTS
 REQUIRED.
  
 TEST REPORTS ARE REQUIRED - MANUFACTURER SPEC SHEETS
 ARE NOT ACCEPTABLE DUE TO DISCREPANCIES BETWEEN SPEC
 SHEETS/BROCHURES AND TEST REPORTS FOR SOME
 MANUFACTURERS (NOT NECESSARILY THE MANUFACTURER
 SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC B 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC B 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC B 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 EXCEPTION IN FBC B 603.1 IS FOR BUILDING TYPE I & II.
 IF THE BUILDING IS III, IV, V, PER FBC B 720.2 FLAME
 SPREAD LESS THAN 25 IS REQUIRED.
  
  
  