Plan Review Notes For Permit 17110126 |
Permit Number |
17110126 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2018-04-27 17:05:03 | 2ND REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION, | | EXISTING BUILDING CODES | | PERMIT #17110126 | | 4/27/18 | | | | PLAN REVIEW RESULTS | | | | 1) THE ENERGY COMPLIANCE FORMS MUST BE THE R405-2014 | | VERSIONS, AND MUST BE SIGNED BY THE PERSON WHO PREPARED | | THE FORMS AND BY THE OWNER- SEE SECTION R103.1.1.2 | | FBC-14 ENERGY CONSERVATION. | | | | 2) M-1: A 4" CLEARANCE IS REQUIRED AROUND THE | | AIRHANDLER- PLEASE CORRECT THE NOTE SPECIFYING 2"-, AND | | VERIFY THE CONDENSATE PIPING IN THE AC CLOSET IS | | NON-COMBUSTIBLE- SECTIONS 602.2 AND 603.1.1. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|