2018-04-27 17:05:032ND REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION,
 EXISTING BUILDING CODES
 PERMIT #17110126
 4/27/18
  
 PLAN REVIEW RESULTS
  
 1) THE ENERGY COMPLIANCE FORMS MUST BE THE R405-2014
 VERSIONS, AND MUST BE SIGNED BY THE PERSON WHO PREPARED
 THE FORMS AND BY THE OWNER- SEE SECTION R103.1.1.2
 FBC-14 ENERGY CONSERVATION.
  
 2) M-1: A 4" CLEARANCE IS REQUIRED AROUND THE
 AIRHANDLER- PLEASE CORRECT THE NOTE SPECIFYING 2"-, AND
 VERIFY THE CONDENSATE PIPING IN THE AC CLOSET IS
 NON-COMBUSTIBLE- SECTIONS 602.2 AND 603.1.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  