2018-02-28 08:12:06 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| SATISFACTORILY HAVE BEEN NOTED AS CORRECTED. ITEMS |
| REMAINING HAVE FURTHER COMMENTS IN PARENTHESES. |
| |
| 1. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| LOADS. THE LOAD CALCULATION PROVIDED USED A DEMAND |
| FACTOR FOR EACH UNIT, AND THEN USED THOSE NUMBERS TO |
| APPLY A SECOND DEMAND FACTOR FOR MULTI-FAMILY |
| DWELLINGS, WHICH IS NOT PERMITTED. ADDITIONALLY, I DO |
| NOT SEE ANY HOUSE PANEL LOADS ADDED. WILL THERE BE ANY |
| HOUSE LOADS INCLUDING LIGHTING OF EXTERIOR? FBC |
| 107.2.1; NEC 220.40 (NEC 220.83 CANNOT BE USED FOR THIS |
| PROJECT, IT IS ONLY FOR A ONE FAMILY DWELLING WHERE |
| LOAD IS TO BE ADDED. PROVIDE ACCURATE LOAD CALCULATION |
| AS REQUESTED.) |
| 2. CORRECTED. |
| 3. BASED ON THE LOADS PROVIDED, THE PROPOSED SERVICE IS |
| NOT ADEQUATE FOR THE LOADS. PROVIDE CORRECTION. NEC |
| 215.2, 215.3, 220.40 (BASED ON MY CALCULATION FROM THE |
| LOADS PROVIDED ON PLAN, THE MINIMUM SERVICE WOULD NEED |
| TO HAVE A CAPACITY OF AT LEAST 886 AMPS. SERVICE |
| DESIGNED IS NOT ADEQUATE FOR THE LOADS SPECIFIED.) |
| 4. PROVIDE ACCURATE RISER DIAGRAM. BASED ON SITE VISIT, |
| THE EXISTING MAIN IS 400 AMPS, NOT 800. IS THE PROPOSED |
| SERVICE JUST A DISCONNECT, OR DOES IT HAVE BREAKERS |
| THAT FEED THE METER STACKS? HOW ARE THE METER STACKS |
| FED? IS THERE A GUTTER WITH TAPS? WHAT IS THE PHYSICAL |
| LOCATION OF ALL THE METERS? RISER PROVIDED DOES NOT |
| HAVE ENOUGH INFORMATION. PROVIDE CLARIFICATION. FBC |
| 107.2.1; NEC 215.5 (MANY OF THE QUESTIONS IN THIS |
| PARAGRAPH ARE NOT ANSWERED WITH YOUR RESPONSE TO ?SEE |
| E-1?. PROVIDE DETAILS AS REQUESTED.) |
| 5. IF METER BANKS ARE ALL TAPPED FROM 800 AMP MAIN, |
| PROVIDE LOAD CALCULATION FOR EACH SET OF FEEDERS TO |
| CONFIRM THE FEEDER IS SIZED ADEQUATELY. NEC 215.2, |
| 220.40 (LOAD CALCULATION TO EACH OF THE 8 METER BANKS |
| IS NOT CORRECT AND WIRE IS NOT SIZED PROPERLY.) |
| 6. GROUNDING ELECTRODE CONDUCTOR SPECIFIED IS NOT SIZED |
| PROPERLY. PROVIDE CORRECTION. NEC 250.66 |
| 7. SHOW LOCATION OF SERVICE ON PLAN. FBC 107.2.1 (NOT |
| CORRECTED.) |
| 8. SHOW LOCATION OF NEW CU UNITS ON PLAN. PROVIDE GFCI |
| PROTECTED OUTLET FOR SERVICING OF A/C EQUIPMENT PER |
| CODE. NEC 210.63; FBC 107.2.1 (NOT PROVIDED) |
| 9. PROVIDE COPY OF SIGNED CONTRACT FOR ELECTRICAL WORK, |
| SHOWING TOTAL VALUE OF ALL WORK INCLUDING MATERIALS AND |
| LABOR. THE ESTIMATE PROVIDED IS TOO LOW AND DOES NOT |
| REFLECT THE AMOUNT OF WORK REQUIRED FOR THIS PROJECT. |
| FBC 109.3 (CONTRACT PROVIDED DOES NOT INCLUDE WORK TO |
| SERVICE. PROVIDE CORRECTION) |
| 10. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| SERVICE (SHOW ON PLAN). THIS IS NOT A WIRE, BUT AN |
| ACTUAL TERMINATION POINT. SEE CODE. NEC 250.94 (NOT |
| SHOWN ON PLAN) |
| |
| NEW COMMENT: |
| |
| 11. PROVIDE SPECS FOR MECHANICAL EQUIPMENT TO CONFIRM |
| STATED DEMAND IS ACCURATE. NEC 110.3, 220; FBC 107.2.1 |
| 12. PLEASE BE ADVISED THAT SOME OF THE COMMENTS HAVE |
| NOT BEEN ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD |
| REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN |
| A THIRD TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN |
| REVIEW IS REQUIRED. FLORIDA STATUTES STATE: WITH |
| RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B) |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |