2018-02-28 08:12:06CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY HAVE BEEN NOTED AS CORRECTED. ITEMS
 REMAINING HAVE FURTHER COMMENTS IN PARENTHESES.
  
 1. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. THE LOAD CALCULATION PROVIDED USED A DEMAND
 FACTOR FOR EACH UNIT, AND THEN USED THOSE NUMBERS TO
 APPLY A SECOND DEMAND FACTOR FOR MULTI-FAMILY
 DWELLINGS, WHICH IS NOT PERMITTED. ADDITIONALLY, I DO
 NOT SEE ANY HOUSE PANEL LOADS ADDED. WILL THERE BE ANY
 HOUSE LOADS INCLUDING LIGHTING OF EXTERIOR? FBC
 107.2.1; NEC 220.40 (NEC 220.83 CANNOT BE USED FOR THIS
 PROJECT, IT IS ONLY FOR A ONE FAMILY DWELLING WHERE
 LOAD IS TO BE ADDED. PROVIDE ACCURATE LOAD CALCULATION
 AS REQUESTED.)
 2. CORRECTED.
 3. BASED ON THE LOADS PROVIDED, THE PROPOSED SERVICE IS
 NOT ADEQUATE FOR THE LOADS. PROVIDE CORRECTION. NEC
 215.2, 215.3, 220.40 (BASED ON MY CALCULATION FROM THE
 LOADS PROVIDED ON PLAN, THE MINIMUM SERVICE WOULD NEED
 TO HAVE A CAPACITY OF AT LEAST 886 AMPS. SERVICE
 DESIGNED IS NOT ADEQUATE FOR THE LOADS SPECIFIED.)
 4. PROVIDE ACCURATE RISER DIAGRAM. BASED ON SITE VISIT,
 THE EXISTING MAIN IS 400 AMPS, NOT 800. IS THE PROPOSED
 SERVICE JUST A DISCONNECT, OR DOES IT HAVE BREAKERS
 THAT FEED THE METER STACKS? HOW ARE THE METER STACKS
 FED? IS THERE A GUTTER WITH TAPS? WHAT IS THE PHYSICAL
 LOCATION OF ALL THE METERS? RISER PROVIDED DOES NOT
 HAVE ENOUGH INFORMATION. PROVIDE CLARIFICATION. FBC
 107.2.1; NEC 215.5 (MANY OF THE QUESTIONS IN THIS
 PARAGRAPH ARE NOT ANSWERED WITH YOUR RESPONSE TO ?SEE
 E-1?. PROVIDE DETAILS AS REQUESTED.)
 5. IF METER BANKS ARE ALL TAPPED FROM 800 AMP MAIN,
 PROVIDE LOAD CALCULATION FOR EACH SET OF FEEDERS TO
 CONFIRM THE FEEDER IS SIZED ADEQUATELY. NEC 215.2,
 220.40 (LOAD CALCULATION TO EACH OF THE 8 METER BANKS
 IS NOT CORRECT AND WIRE IS NOT SIZED PROPERLY.)
 6. GROUNDING ELECTRODE CONDUCTOR SPECIFIED IS NOT SIZED
 PROPERLY. PROVIDE CORRECTION. NEC 250.66
 7. SHOW LOCATION OF SERVICE ON PLAN. FBC 107.2.1 (NOT
 CORRECTED.)
 8. SHOW LOCATION OF NEW CU UNITS ON PLAN. PROVIDE GFCI
 PROTECTED OUTLET FOR SERVICING OF A/C EQUIPMENT PER
 CODE. NEC 210.63; FBC 107.2.1 (NOT PROVIDED)
 9. PROVIDE COPY OF SIGNED CONTRACT FOR ELECTRICAL WORK,
 SHOWING TOTAL VALUE OF ALL WORK INCLUDING MATERIALS AND
 LABOR. THE ESTIMATE PROVIDED IS TOO LOW AND DOES NOT
 REFLECT THE AMOUNT OF WORK REQUIRED FOR THIS PROJECT.
 FBC 109.3 (CONTRACT PROVIDED DOES NOT INCLUDE WORK TO
 SERVICE. PROVIDE CORRECTION)
 10. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE (SHOW ON PLAN). THIS IS NOT A WIRE, BUT AN
 ACTUAL TERMINATION POINT. SEE CODE. NEC 250.94 (NOT
 SHOWN ON PLAN)
  
 NEW COMMENT:
  
 11. PROVIDE SPECS FOR MECHANICAL EQUIPMENT TO CONFIRM
 STATED DEMAND IS ACCURATE. NEC 110.3, 220; FBC 107.2.1
 12. PLEASE BE ADVISED THAT SOME OF THE COMMENTS HAVE
 NOT BEEN ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD
 REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN
 A THIRD TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN
 REVIEW IS REQUIRED. FLORIDA STATUTES STATE: WITH
 RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  