2017-12-27 09:14:03 | ****PLAN REVIEW COMMENTS**** |
| |
| ART LANGE BUILDING PLANS EXAMINER |
| |
| DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS STREET |
| WEST PALM BEACH, FL 33402 |
| |
| 561-805-6667 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2014 5TH EDITION/ FRC FLORIDA |
| RESIDENTIAL CODE 2015 5TH EDITION |
| |
| SECOND REVIEW: |
| |
| 1. PROVIDE TWO COPIES OF THE SOUND PROOFING |
| SPECIFICATIONS FOR THE SECOND FLOOR APARTMENTS THAT |
| SHOW COMPLIANCE WITH THE FOLLOWING STANDARDS. |
| |
| FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E - 492-09 |
| |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| |
| 2. OK ADDRESSED. |
| |
| 3. PERMIT VALUE ADJUSTED PER ESTIMATE SUBMITTED. OK. |
| |
| 4. OK ADDRESSED. |
| |
| |
| |
| WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: |
| |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. |
| WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED |
| SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS |
| READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE |
| RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE |
| FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR |
| *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN |
| THE PERMIT PACKAGE. |
| |
| A RESPONSE LETTER INDICATING HOW EACH ITEM WAS |
| ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. |
| |
| |