2018-01-02 14:13:30 | 1ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION, |
| EXISTING BUILDING CODES |
| PERMIT #17110126 |
| 1/2/2018 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW |
| AC SYSTEMS- SEE SECTIONS C403.2.1 AND C407.5.2.3 ENERGY |
| CONSERVATION. |
| |
| 2) REFER TO SECTION C101.4.5 FBC-14 ENERGY CONSERVATION |
| AND SUBMIT AN ENERGY COMPLIANCE REPORT FOR THE |
| BUILDING. |
| |
| 3) SHEET M-1: NATURAL OR MECHANICAL VENTILATION IS |
| REQUIRED FOR EACH APARTMENT PER SECTION 401.2. PLEASE |
| INDICATE WHICH METHOD WILL BE USED AND PROVIDED |
| CALCULATIONS AND DETAILS. |
| |
| 4) M-1: NO SUPPLY AND RETURN AIR IS SHOWN FOR THETYPE A |
| APARTMENT BEDROOMS 1 & 2, AND NO SUPPLY IS PROVIDED TO |
| THE TYPE B KITCHEN/LIVING/DINING ROOMS- SEE SECTION |
| 601.5 FBC-14 MECHANICAL AND CORRECT. |
| |
| 5) M-1: VERIFY THE AC CLOSET DOORS ARE NON-COMBUSTIBLE |
| IN ACCORDANCE WITH SECTION C403.2.7.2 FBC-14 ENERGY |
| CONSERVATION CODE, AND SECTION 602.2.1 FBC-14 |
| MECHANICAL. |
| |
| 6) M-1: AN INCORRECT WIND SPEED OF 160 MPH IS NOTED. |
| PLEASE NOTE THAT THE WIND SPEED IN WEST PALM BEACH IS |
| 170 MPH. CORRECT THE NOTE AND PROVIDE COMPLETE WIND |
| LOAD DESIGN CRITERIA INCLUDING THE IMPORTANCE FACTOR, |
| EXPOSURE CATEGORY, AND THE LATERAL AND UPLIFT |
| PRESSURES. |
| |
| 7) PROVIDE A MECHANICAL SITE PLAN THAT SHOWS THE |
| LOCATIONS OF ALL THE CONDENSERS AND THE REFRIGERANT |
| PIPING RUNS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |