2017-11-20 15:52:31 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND |
| SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE |
| ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H); |
| 471.025; FBC 107.2.1, 107.3.5 |
| 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| WITH CODE. NEC 210.8, 210.12, 215.5, 408.4 |
| 3. SHOW ON FLOOR PLAN ALL EXISTING SMOKE ALARMS. IF |
| NONE ARE EXISTING, OR NOT TO CODE, SHOW AS NEW |
| INSTALLATION. FBC 107.2.1 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |