Plan Review Notes For Permit 17110125 |
Permit Number |
17110125 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-11-28 11:13:22 | 4610 BROADWAY | | PERMIT #17110125 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | PROVIDE NONCOMBUSTIBLE FLAME CERTIFICATE FOR THE TENT | | MATERIAL. | | | | EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS ARE | | REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET. | | | | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE | | OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS. | | | | TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM | | BUILDING STRUCTURES. | | | | POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS | | LOCATIONS. | | | | PROVIDE A FLOOR PLAN FOR THE TENT INDICATING EXITS, | | EXIT SIGNS, EMERGENCY LIGHTING, COOKING APPLIANCES, | | GENERATORS, SEATING, DANCE FLOOR, ETC. | | | | A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED | | AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON | | THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED DURING PLAN RESUBMISSION. | | | | WESLEY JOLIN | | ASSISTANT FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | |
|