2018-05-12 05:25:23 | 1) THERE ARE TWO SETS OF PLANS THAT ARE MISSING THE |
| "CVR" SHEET AND ALSO THE ELECTRICAL PLANS. SUBMIT TWO |
| COMPLETE SETS OF PLANS FOR REVIEW. WPB AMEND TO FBC |
| SEC. 107.1. |
| 2) ONE SET OF PLANS CONTAINS MEP SHEETS THAT ARE NOT |
| SIGNED AND SEALED BY THE DESIGN PROFESSIONAL. COMPLY |
| WITH FL. ADMIN. CODE RULE 61G15-23.001. |
| 3) SHT. A1.0 - DETAIL #3 - ENLARGED PLAN - THE |
| ELEVATION ARROWS LISTING THE ELEVATION DETAIL DO NOT |
| CORRELATE WITH THE ELEVATIONS ON THE PLANS AND ALSO |
| REFER TO SHT. A4 WHICH THERE IS NO SUCH SHEET. REVISE. |
| WPB AMEND. TO FBC SEC. 107.2.1. |
| 4) SHT. A1.0 - THE OUTLET OF THE TOILET PAPER DISPENSER |
| IN THE HANDICAPPED TOILET ROOMS SHALL BE LOCATED A |
| MINIMUM OF 15 INCHES AND A MAXIMUM OF 48 INCHES ABOVE |
| THE FINISH FLOOR. 2017 FBC-ACCESS. SEC.604.7. SHOW THIS |
| ON SHT. A1.0. |
| 5) SHOW THE REQUIRED TURNING SPACE IN RESTROOM #105 IN |
| ACCORDANCE WITH THE 2017 FBC-ACCESS. SEC.304.1, |
| 304.3.1, 304.3.2. |
| 6) SHT. A1.0 - RESTROOM #105 - SHOW THE WIDTH DIMENSION |
| BETWEEN THE CORNER EDGE OF THE LAVATORY AND THE END OF |
| THE URINAL PARTITION.COMPLY WITH 2017 FBC-ACCESS. |
| SEC.305.3. |
| 7) SUBMIT 2 COMPLETE COPIES OF THE MANUFACTURER'S |
| INSTALLATION MANUAL FOR THE DISHWASHER. WPB AMEND. TO |
| FBC SEC. 107.2.1. 2ND REQUEST. |
| 8) SHT. P-2 - INDICATE ON THE EXPANSION TANK SIZING |
| CHART ON SHT. P-2 THE SIZE OF THE EXPANSION TANK TO BE |
| INSTALLED ON THE WATER SUPPLY SYSTEM. |
| 9) SUBMIT TWO COPIES OF THE INSTALLATION MANUAL FOR THE |
| WATER FILTRATION SYSTEM. WPB AMEND. TO FBC SEC. |
| 107.2.1. 2ND REQUEST. |
| 10) SHT. A1.0 - DETAIL #4 - THE LOCATION OF THE SIDE |
| GRAB BAR SHALL COMPLY WITH 2017 FBC-ACCESS. |
| SEC.604.5.1. THE GRAB BAR SHALL EXTEND A MINIMUM OF 54 |
| INCHES FROM THE REAR WALL. REFER TO 2017 FBC-ACCESS. |
| FIGURE 604.5.1.3RD REQUEST. |
| 11) SHT. P-2 - THE DISCHARGE LIINE FROM THE WORK TABLE |
| IN BOH #103 SHALL BE INDIRECTLY WASTED TO THE GREASY |
| WASTE SYSTEM PER THE 2017 FBC-PLUMBING SEC.802.2. |
| 12) SUBMIT AN EXPANDED PIPNG DETAIL / DIAGRAM FOR THE |
| HOT WATER RECIRCULATION SYSTEM. THE HOT WATER OR |
| TEMPERED WATER RETURN LINE SHALL BE INSTALLED IN |
| ACCORDANCE WITH THE 2017 FBC-PLUMBING SEC.607.2.2. A |
| NOTE HAS BEEN PLACED ON THE PLAN TO THIS EFFECT BUT IS |
| INADEQUATE. I HAVE INCLUDED A DIAGRAM AND TEXT FROM THE |
| PLUMBING CODE COMMENTARY IN THE PLAN REVIEW FOLDER FOR |
| A REFERENCE.2ND REQUEST. |
| 13) NOTE: ALL PLUMBING PIPES SHALL BE EXPOSED AND |
| TESTED FOR INSPECTION OR A VIDEO OF SANITARY PIPING |
| SHALL BE APPROVED BY TIM LARGE FOR THE ROUGH |
| INSPECTIONS PER FBC PL 312. ROUGH INSPECTION WILL NOT |
| PASS IF THE VIDEO SSHOWS ANY PORTION OF THE UNDERGROUND |
| PIPING EXHIBITING NON-COMPLIANCE WITH THE PLUMBING CODE |
| AND IN THAT INSTANCE THE UNDERSLAB PIPING SHALL BE |
| EXPOSED FOR AND CORRECTED AND INSPECTED FOR COMPLIANCE. |
| |