Plan Review Notes
Plan Review Notes For Permit 17110117
Permit Number 17110117
Review Stop E
Sequence Number 3
Notes
Date Text
2018-05-22 13:47:35CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: OK, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED
 7. CORRECTED
 8. CORRECTED.
 9. CORRECTED.
 10. CORRECTED.
 11. CORRECTED.
 12. CORRECTED
  
 NEW COMMENT:
  
 13. IT APPEARS THAT THERE IS A TABLE IN FRONT OF
 ELECTRICAL PANELS. CLEARANCE IN FRONT OF PANELS IS
 REQUIRED PER NEC, PROVIDE CORRECTION. NEC 110.26
 14. CORRECTED
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER ,CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  
  
2018-05-15 09:27:24CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED
 IN THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE
 AUTOMATIC CONTROL REQUIRED. FBC CE 405.2.2, 405.2.2.2
 (NOT PROVIDED. A GENERAL NOTE IS NOT ACCEPTABLE,
 PROVIDE DETAILS OF LIGHTING CONTROL ON PLAN.)
 7. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS WHERE APPLICABLE FOR LOW VOLTAGE SYSTEMS,
 FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS,
 WALK-IN COOLERS, HOODS, ETC. FBC 105.1, 107.2.1 (NOT
 PROVIDED.)
 8. CORRECTED.
 9. CORRECTED.
 10. CORRECTED.
 11. CORRECTED.
 12. PROVIDE AUTOMATIC CONTROL FOR SIGN AND SHOW WINDOW
 LIGHTING. LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN
 OPERATION SHALL BE CONTROLLED BY EITHER A COMBINATION
 OF A PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL
 TIME SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN
 OPERATION SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME
 SWITCH OR PHOTOSENSOR. ALL TIME SWITCHES SHALL BE
 CAPABLE OF RETAINING PROGRAMMING AND THE TIME SETTING
 DURING LOSS OF POWER FOR A PERIOD OF AT LEAST 10 HOURS.
 FBC CE 405.2.4 (NOT PROVIDED. A GENERAL NOTE IS NOT
 ACCEPTABLE, PROVIDE DETAILS OF LIGHTING CONTROL ON
 PLAN.)
  
 NEW COMMENT:
  
 13. IT APPEARS THAT THERE IS A TABLE IN FRONT OF
 ELECTRICAL PANELS. CLEARANCE IN FRONT OF PANELS IS
 REQUIRED PER NEC, PROVIDE CORRECTION. NEC 110.26
 14. ONLY ONE SET OF PLANS WAS PROVIDED FOR REVIEW, AND
 THE PLAN IS NOT SIGNED AND SEALED BY THE DESIGN
 PROFESSIONAL. PROVIDE CORRECTION. WPB FBC 107.1, 107.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  