Plan Review Notes For Permit 17110117 |
Permit Number |
17110117 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2018-05-16 12:00:22 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | BUILDING REVIEW IS NOT ENTIRELY COMPLETE, BUT I'LL WORK | | WITH APPLICANT VIA EMAIL TO GET ALL OUTSTANDING ISSUES | | RESOLVED. | | | | WE DISAGREE THAT THIS IS STRUCTURALLY INFEASIBLE; A | | PLAN WILL BE SENT VIA EMAIL TO MIGUEL (ARCHITECT'S | | OFFICE). | | | | AS DISCUSSED, PLEASE PROVIDE A DETAILED COST BREAKDOWN | | COST TO PROVIDE AN ACCESSIBLE ENTRANCE AND PROJECT COST | | (DISPROPORTIONATE COST). | | | | ALSO DISCUSSED WAS THE ISSUE OF: WE BELIEVE IT IS | | POSSIBLE THAT THERE WERE STEPS AT THIS LOCATION, AND | | WAS CONVERTED WITHOUT A PERMIT TO A NON COMPLIANT RAMP | | (OVER 14% SLOPE). THEREFORE, THE UNSAFE ENTRANCE IS NOT | | GRANDFATHERED IN VIA EXISTING BUILDING CODE AS IT WAS | | NOT BUILT IN COMPLIANCE WITH CODE IN EFFECT WHEN | | BUILDING WAS BUILT. | | | | A PRELIMINARY DETAIL WILL BE REVIEWED VIA EMAIL. | | | | FOR CODE SECTIONS, SEE FIRST REVIEW. |
|