2018-04-03 15:23:16 | 2ND REVIEW |
| |
| PLUMBING COMMENTS: |
| |
| 1. THE PREVIOUS OCCUPANCY OF THIS TENANT SPACE WAS |
| MERCANTILE WHICH MAKES THIS A CHANGE OF OCCUPANCY. IN |
| ADDITION, THIS IS ALSO CONSIDERED A LEVEL 3 ALTERATION |
| BECAUSE THE ENTIRE AREA HAS BEEN ALTERED. THEREFORE THE |
| REQUIREMENTS OF CHAPTER 10 OF THE 2017 FBC-EXISTING |
| BUILDING CODE APPLIES TO THIS STRUCTURE, AND CHAPTERS |
| 7, 8 AND 9 WILL ALSO APPLY. PLEASE REVISE |
| CLASSIFICATION OF WORK ON SHT. ALS 1.1 TO READ THAT |
| THIS IS A CHANGE OF OCCUPANCY.PLACE THE PREVIOUS |
| OCCUPANCY ON THE PLAN. WPB AMEND. TO FBC SEC. 107.2.1, |
| 107.3.5.1.1. 2ND REQUEST. |
| |
| 2. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.5.1 FOR THE |
| GRAB BAR LOCATED ON THE SIDE WALL OF THE WATER CLOSET. |
| SEE FIGURE 604.5.1. |
| THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG MINIMUM, |
| LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL AND |
| EXTENDING 54 INCHES |
| MINIMUM FROM THE REAR WALL. 2ND REQUEST. |
| |
| 3. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.5.2 FOR THE |
| GRAB BAR LOCATED ON THE REAR WALL OF THE WATER CLOSET. |
| SEE FIGURE 604.5.2. |
| THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG MINIMUM |
| AND EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12 |
| INCHES MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE |
| OTHER SIDE. 2ND REQUEST. |
| |
| 4. AT LEAST ONE OF THE URINALS SHALL COMPLY WITH FBC |
| ACC 605.2 HEIGHT AND DEPTH. |
| URINALS SHALL BE THE STALL-TYPE OR THE WALL-HUNG TYPE |
| WITH THE RIM 17 INCHES MAXIMUM ABOVE THE FINISH FLOOR |
| OR GROUND. URINALS SHALL BE 13 1/2 INCHES DEEP MINIMUM |
| MEASURED FROM THE OUTER FACE OF THE URINAL RIM TO THE |
| BACK OF THE FIXTURE. |
| 605.3 CLEAR FLOOR SPACE. |
| A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305 |
| POSITIONED FOR FORWARD APPROACH SHALL BE PROVIDED. 2ND |
| REQUEST. |
| |
| 5. SHOW THE PLUMBING FIXTURE CLEARANCES FOR THE URINALS |
| IN ACCORDANCE WITH 2017 FBC-PLUMBING SEC.405.3.1. |
| |
| 6. SHT. A1.0 - SHOW THE LENGTH AND WIDTH DIMENSIONS OF |
| THE CLEAR FLOOR SPACES IN THE HANDICAPPED TOILET ROOMS. |
| CLEAR FLOOR SPACE DIMENSIONS FOR THE WATER CLOSET SHALL |
| COMPLY WITH 2017 FBC-ACCESS. SEC.604.3.1. CLEAR FLOOR |
| SPACE FOR THE LAVATORIES SHALL COMPLY WITH SECS. 305, |
| 606.2. ALSO, SHOW THE DIMENSIONS OF THE CLEAR FLOOR |
| SPACE LOCATED BEYOND THE ARC OF THE DOOR SWING. COMPLY |
| WITH 2017 FBC - ACCESS. SEC. 305.3. |
| |
| 7. PLEASE SHOW COMPLIANCE WITH FBC PL 405.3.5 URINAL |
| PARTITIONS. |
| EACH URINAL UTILIZED BY THE PUBLIC OR EMPLOYEES SHALL |
| OCCUPY A SEPARATE AREA WITH WALLS OR PARTITIONS TO |
| PROVIDE PRIVACY. THE WALLS OR PARTITIONS SHALL BEGIN AT |
| A HEIGHT NOT GREATER THAN 12 INCHES FROM AND EXTEND NOT |
| LESS THAN 60 INCHES ABOVE THE FINISHED FLOOR SURFACE. |
| THE WALLS OR PARTITIONS SHALL EXTEND FROM THE WALL |
| SURFACE AT EACH SIDE OF THE URINAL NOT LESS THAN 18 |
| INCHES OR TO A POINT NOT LESS THAN 6 INCHES BEYOND THE |
| OUTERMOST FRONT LIP OF THE URINAL MEASURED FROM THE |
| FINISHED BACKWALL SURFACE, WHICHEVER IS GREATER. 2ND |
| REQUEST. |
| |
| 8. SHT. A1.0 SHOWS ROOM #105 WITH TWO URINALS AND A |
| LAVATORY AS "PRIVATE". THIS ROOM DOES NOT MEET THE |
| DEFINITION OF "PRIVATE" IN SEC. 202 OF THE 2017 FBC - |
| PLUMBING. THIS RESTROOM IS LOCATED IN A COMMON AREA AND |
| SHALL BE OPEN AND ACCESSIBLE TO THE OCCUPANTS OF THIS |
| SPACE AND SHALL FULLY COMPLY WITH 2017 FBC-ACCESS. SEC. |
| 213.2 AND 2017 FBC-PLUMBING SEC.405.3.1. |
| |
| 9. THE LAVATORY IN ROOM #105 ( "PRIIVATE RESTROOM") |
| SHALL COMPLY WITH THE 2017 FBC-ACCESS. SECS.213.3.4, |
| 305, & 606. |
| |
| 10. THE HAND DRYER IN ROOM #105 SHALL COMPLY WITH 2017 |
| FBC -ACCESS. SECS. 308 & 309. |
| |
| 11. SHT. A1.0 - NOTE #6 REFERS TO THE 2010 |
| ACCESSIBILITY CODE. THE 2017 FBC-ACCESS. IS THE CODE IN |
| EFFECT FOR THIS PROJECT. PLEASE REVISE THE NOTE. |
| |
| 12. THE FLOOR SINKS, FLOOR DRAIN AND SINKS IN THE |
| SERVICE AREA # 102 AND THE WORKTABLE SINK IN BOH #103 |
| SHALL DISCHARGE THROUGH THE GREASE INTERCEPTOR PER THE |
| 2017 FBC-PLUMBING SEC. 1003.3.1. THE ICE WELLS SHALL |
| DISCHARGE TO THE SANITARY SYSTEM PER 2017 FBC-PLUMBING |
| SEC.1003.2. |
| |
| 13. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WATER |
| HEATER.2017 FBC-PLUMBING SEC.501. |
| |
| 14. SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| SPECIFICATIONS/INSTALLATION INSTRUCTIONS FOR THE GREASE |
| INTERCEPTOR. 2017 FBC-PLUMBING SEC.1003.2. |
| |
| 15. INDICATE THE SIZE OF THE EXPANSION TANK ON THE |
| WATER HEATER. THE EXPANSION TANK SHALL BE SIZED IN |
| ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS PERR |
| 2017 FBC-PLUMBING SEC.607.3. SUBMIT TWO COPIES OF |
| MANUFACTURER'S INSTRUCTIONS. SHOW THE CAPACITY OF THE |
| WATER HEATER IN GALLONS ON THE PLANS. |
| |
| 16. SINKS USED FOR THE WASHING, RINSING,OR SANITIZING |
| OF UTENSILS, DISHES, POTS, PANS OR SERVICE WARE USED IN |
| THE PREPARATION, SERVING OR EATING OF FOOD SHALL |
| DISCHARGE INDIRECTLY THROUGH AN AIR GAP OR AIR BREAK TO |
| THE DRAINAGE SYSTEM PER 2017 FBC-PLUMBING SEC.802.2. (3 |
| COMPARTMENT SINK). |
| |
| 17. THE DRAIN FOR THE INDIRECT WASTE FOR THE WARE |
| WASHER AND PIZZA OVEN SHALL BE EQUIPPED WITH A TRAP. |
| 2017 FBC - PLUMBING SEC.301 & 802.2. |
| |
| 18. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WATER |
| FILTRATION SYSTEM. WPB AMEND. TO FBC SEC. 107.2.1, 2017 |
| FBC-PLUMBING SEC. 611.1. |
| |
| 19. SUBMIT A PIPING DETAIL OF THE HOT WATER |
| RECIRCULATION SYSTEM. THE HOT WATER OR TEMPERED WATER |
| RETURN LINE SHALL BE INSTALLED IN ACCORDANCE WITH 2017 |
| FBC-PLUMBING SEC.607.2.2. SHOW ON THE DETAIL WHERE/HOW |
| THE 140 DEGREE HOT WATER IS CONNECTED TO THE WATER |
| HEATER . IT IS UNCLEAR ON THE WATER RISER. |
| |
| 20. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| DISHWASHER. THE DISHWASHER SHALL COMPLY WITH 2017 |
| FBC-PLUMBING SEC.409. |
| |
| 21. HOT WATER PIPING SHALL BE INSULATED IN ACCORDANCE |
| WITH 2017 FBC-ENERGY TABLE C403.2.10, NOT TABLE |
| C403.2.8 AS NOTED ON SHT.P-3. |
| |
| 22. ALL PLUMBING PIPES SHALL BE EXPOSED AND TESTED FOR |
| INSPECTION OR A VIDEO OF SANITARY PIPING SHALL BE |
| APPROVED BY TIM LARGE FOR THE ROUGH INSPECTIONS. PER |
| FBC PL 312 |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |
| 561-805-6692 |
| [email protected] |
| |