Plan Review Notes
Plan Review Notes For Permit 17110117
Permit Number 17110117
Review Stop M
Sequence Number 2
Notes
Date Text
2018-04-09 08:12:112ND REVIEW FBC-2014 MECHANICAL, WEST PALM BEACH
 AMENDMENTS TO THE FBC-14
 PERMIT #17110117
 4/9/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: PLEASE LABEL THE OFFICE ON THE MECHANICAL
 PLAN- SECTION 107.2.1 WPB AMENDMENTS.
  
 2) M-1: INDICATE HOW THE BACK OF THE HOUSE AREA IS
 BEING VENTILATED- TABLE 403.3.
  
 3) PROVIDE AN AIR BALANCE CALCULATION- SECTION 508.1.2.
  
 4) THE CITY OF WPB PERMITTING RECORDS DO NOT SHOW ANY
 PERMITS FOR THE RTU'S, THE MINI-SPLIT SYSTEM, AND THE
 WALK-IN COOLER, THEREFORE THESE SYSTEMS SHALL BE
 REVIEWED AND PERMITTED AS NEW. PLEASE PROVIDE:
  
 A) EQUIPMENT SCHEDULES ON THE PLAN FOR THE SYSTEMS.
 B) AC COOLING AND HEATING CALCULATIONS.
 C) CONDENSATE DISPOSAL PLANS.
  
 PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR THE
 WALK-IN COOLER, AND THE PIZZA OVEN AND EXHAUST SYSTEM.
  
 5) M-1 & M-2: SHOW THE LOCATION OF THE AC STAND AND
 WHAT UNIT IT IS SUPPORTING- SECION 107.2.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  