2018-04-09 08:12:11 | 2ND REVIEW FBC-2014 MECHANICAL, WEST PALM BEACH |
| AMENDMENTS TO THE FBC-14 |
| PERMIT #17110117 |
| 4/9/18 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M-1: PLEASE LABEL THE OFFICE ON THE MECHANICAL |
| PLAN- SECTION 107.2.1 WPB AMENDMENTS. |
| |
| 2) M-1: INDICATE HOW THE BACK OF THE HOUSE AREA IS |
| BEING VENTILATED- TABLE 403.3. |
| |
| 3) PROVIDE AN AIR BALANCE CALCULATION- SECTION 508.1.2. |
| |
| 4) THE CITY OF WPB PERMITTING RECORDS DO NOT SHOW ANY |
| PERMITS FOR THE RTU'S, THE MINI-SPLIT SYSTEM, AND THE |
| WALK-IN COOLER, THEREFORE THESE SYSTEMS SHALL BE |
| REVIEWED AND PERMITTED AS NEW. PLEASE PROVIDE: |
| |
| A) EQUIPMENT SCHEDULES ON THE PLAN FOR THE SYSTEMS. |
| B) AC COOLING AND HEATING CALCULATIONS. |
| C) CONDENSATE DISPOSAL PLANS. |
| |
| PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR THE |
| WALK-IN COOLER, AND THE PIZZA OVEN AND EXHAUST SYSTEM. |
| |
| 5) M-1 & M-2: SHOW THE LOCATION OF THE AC STAND AND |
| WHAT UNIT IT IS SUPPORTING- SECION 107.2.1. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |