2018-04-12 16:36:052014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17110117
 ADD: 123 DATURA ST.
 CONT: FINE LINE CONSTRUCTION
 TEL: 561-582-7880
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. APRIL 12/ 2018
 ACTION: DENIED
  
 1) PLEASE SUBMIT THE PERMIT APPLICATION AND PLANS NOTED
 UNDER THE PROPER STREET ADDRESS AND TENANT ADDRESS.
 WHEN VIEWING THE TENANT SITE UNDER THE PALM BEACH
 COUNTY PROPERTY APPRAISERS WEBSITE THE BUILDING ADDRESS
 IS 125 DATURA, THE TENANT SPACE OR SUITE WOULD BE 123
 DATURA. PLEASE ADDRESS CORRECTLY.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED.
  
 2014 FBC-B 501.2 ADDRESS IDENTIFICATION. NEW AND
 EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED
 ADDRESS IDENTIFICATION.
  
 2) SHEET ALS1.1:
  
 2A) LIST THE OCCUPANCY AS AN A-2 OCCUPANCY AND A LEVEL
 2 ALTERATION. PLEASE NOTE THE LAST KNOWN USE (LICENSED/
 BUSINESS TAX) WAS BEE ORGANICS AS A MERCANTILE
 OCCUPANCY. PLEASE NOTE THIS IS A CHANGE OF OCCUPANCY
 AND MEET THE REQUIREMENTS OF SECTION 1001.3.1 PARTIAL
 CHANGE OF OCCUPANCY CLASSIFICATION OF THE 2014 EXISTING
 BUILDING CODE.
 1001.3.1 PARTIAL CHANGE OF OCCUPANCY CLASSIFICATION.
 WHERE A PORTION OF AN EXISTING BUILDING IS CHANGED TO A
 NEW OCCUPANCY CLASSIFICATION, SECTION 1012 SHALL APPLY.
 PLEASE UPDATE THE PLANS TO ILLUSTRATE NOT A LEVEL II
 ALTERATION BUT A CHANGE OF OCCUPANCY UNDER CHAPTER 10
 OF THE EXISTING BUILDING CODE.
  
 2B) PLEASE PROVIDE A CODE ANALYSIS OF THE BUILDING AND
 TENANT SPACE. PROVIDE THE FOLLOWING INFORMATION:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILD
 107.3.5.1.1 BUILDING
 OCCUPANCY GROUP
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE
 TABLE 503)
 SQUARE FOOTAGE OF BUILDING
 IS THE BUILDING FIRE SPRINKLERED? IS IT REQUIRED?
 OCCUPANT LOAD PER AREA OR USE OF THE TENANT SPACE A
 THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 2C) THE PLANS ARE SILENT TO HOW TENANT AND OCCUPANCY
 SEPARATION IS HANDLED?
 2014 FBC-EXISTING BUILDING CODE SECTIONS; 1012.1.1
 COMPLIANCE WITH CHAPTER 9 .
 THE REQUIREMENTS OF CHAPTER 9 SHALL BE APPLICABLE
 THROUGHOUT THE BUILDING FOR THE NEW OCCUPANCY
 CLASSIFICATION BASED ON THE SEPARATION CONDITIONS SET
 FORTH IN SECTIONS 1012.1.1.1 AND 1012.1.1.2.
 1012.1.1.1 CHANGE OF OCCUPANCY CLASSIFICATION WITHOUT
 SEPARATION.
 1012.1.1.2 CHANGE OF OCCUPANCY CLASSIFICATION WITH
 SEPARATION.
  
 2D) 2014 EXISTING BUILDING CODE 1012.4.2 MEANS OF
 EGRESS FOR CHANGE OF USE TO EQUAL OR LOWER HAZARD
 CATEGORY. WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS
 MADE TO AN EQUAL OR LESSER HAZARD CATEGORY (HIGHER
 NUMBER) AS SHOWN IN TABLE 1012.4, EXISTING ELEMENTS OF
 THE MEANS OF EGRESS SHALL COMPLY WITH THE REQUIREMENTS
 OF SECTION 905 FOR THE NEW OCCUPANCY CLASSIFICATION.
 NEWLY CONSTRUCTED OR CONFIGURED MEANS OF EGRESS SHALL
 COMPLY WITH THE REQUIREMENTS OF CHAPTER 10 OF THE
 FLORIDA BUILDING CODE, BUILDING.
 PLEASE NOTE THE TABLE AND CHAIR LAYOUT GIVEN HAS A
 HIGHER OCCUPANT LOAD COUNT IF FOR BENCH SEATING IT IS
 TAKEN AT 18 INCHES PER OCCUPANT AND TABLES 6.5 FEET
 LONG ALL TABLES TO BE REPRESENTED WITH 6 OCCUPANTS PER
 TABLE, THE (2) BANQUETS IN THE WINDOW BENCH SEATING AT
 18 INCHES AND SEATING ON THE OPPOSITE SIDE OF THE TABLE
 PLUS AN ADDITIONAL 6 PERSON TABLE BEHIND THE HOSTESS
 STATION. THE OTHER ISSUE IS THE KITCHEN IS TAKEN AT
 1019 SQ. FT. / 200= 4 IT WOULD EQUAL 5.095 OCCUPANTS
 WITH FRACTIONS YOU ALWAYS ROUND UP. THE COOLER IS
 STORAGE OCCUPANCY AND AN OCCUPANT LOAD OF 1 SHOULD BE
 ADDED OR AN OCCUPANT LOAD OF 68 AND WITH 84 OCCUPANTS
 WHEN SEASONAL SEATING IS CONSIDERED FOR THE REQUIRED
 PLUMBING FIXTURE COUNT. 2014 FBC-B 1004.2.
  
 2E) WITH AN OCCUPANT LOAD OF 50 OR MORE (2) MEANS OF
 EGRESS ARE REQUIRED. 2014 FBC-B TABLE 1015.1.
  
 2F) WITH AN OCCUPANT LOAD OF 50 OR MORE (2) MEANS OF
 EGRESS ARE REQUIRED THE 2ND MEANS OF EGRESS CANNOT BE
 THROUGH THE KITCHEN. 2014 FBC-B 1014.2 EGRESS THROUGH
 INTERVENING SPACES. (4) EGRESS SHALL NOT PASS THROUGH
 KITCHENS, STORAGE ROOMS, CLOSETS OR SPACES USED FOR
 SIMILAR PURPOSES.
  
 2G) 2014 FBC-ACCESSIBILITY CODE. 206.4.1 PUBLIC
 ENTRANCES. (DOORWAYS) IN ADDITION TO ENTRANCES REQUIRED
 BY 206.4.2 THROUGH 206.4.9, AT LEAST 60 PERCENT OF ALL
 PUBLIC ENTRANCES SHALL COMPLY WITH 404. 2 X 0.60= 1.2
 OR 2 MEANS OF ACCESSIBLE ENTRANCES / EXITS.
  
 2H) PLEASE PROVIDE THE RISE AND RUN OF THE EXISTING
 RAMP AT THE FRONT ENTRY, IT WOULD APPEAR IT IS STEEPER
 THAN ALLOWED BY THE CODE. PLEASE REVIEW FOR EXISTING
 BUILDINGS THE MAXIMUM RAMP SLOPE AND RISE FOR EXISTING
 BUILDINGS 2014 FBC-ACCESSIBILITY CODE TABLE 405.2.
  
 2I) THE PLANS INDICATE A DOOR AND STAIRWAY INTO THE
 KITCHEN, PLEASE SHOW COMPLIANCE WITH LANDING. 2014
 FBC-B 1009.8 STAIRWAY LANDINGS. THERE SHALL BE A FLOOR
 OR LANDING AT THE TOP AND BOTTOM OF EACH STAIRWAY. THE
 WIDTH OF LANDINGS SHALL NOT BE LESS THAN THE WIDTH OF
 STAIRWAYS THEY SERVE. EVERY LANDING SHALL HAVE A
 MINIMUM WIDTH MEASURED PERPENDICULAR TO THE DIRECTION
 OF TRAVEL EQUAL TO THE WIDTH OF THE STAIRWAY. WHERE THE
 STAIRWAY HAS A STRAIGHT RUN THE DEPTH NEED NOT EXCEED
 48 INCHES.
  
 2J) THE PLANS DO NOT SHOW ANY HANDRAILS ON EITHER SIDE
 OF THE STAIR. 2014 EXISTING BUILDING CODE 805.9.1
 MINIMUM REQUIREMENT. EVERY REQUIRED EXIT STAIRWAY THAT
 IS PART OF THE MEANS OF EGRESS FOR ANY WORK AREA AND
 THAT HAS THREE OR MORE RISERS AND IS NOT PROVIDED WITH
 AT LEAST ONE HANDRAIL, OR IN WHICH THE EXISTING
 HANDRAILS ARE JUDGED TO BE IN DANGER OF COLLAPSING,
 SHALL BE PROVIDED WITH HANDRAILS FOR THE FULL LENGTH OF
 THE RUN OF STEPS ON AT LEAST ONE SIDE.
  
 2K) SHEET ALS1.1 SHOWS STAIRS GOING TO THE KITCHEN BUT
 NO VERTICAL ACCESSIBILITY, PLEASE SHOW COMPLIANCE WITH:
 2014 FBC-ACCESSIBILITY CODE 201.1.1 VERTICAL
 ACCESSIBILITY. SECTIONS 553.501-553.513, F.S., AND THE
 ADA STANDARDS FOR ACCESSIBLE DESIGN DO NOT RELIEVE THE
 OWNER OF ANY BUILDING, STRUCTURE OR FACILITY GOVERNED
 BY THOSE SECTIONS FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE
 OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE
 STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH
 BUILDING, STRUCTURE OR FACILITY, EXCEPT FOR: 3)
 OCCUPIABLE SPACES AND ROOMS THAT ARE NOT OPEN TO THE
 PUBLIC AND THAT HOUSE NO MORE THAN FIVE PERSONS. WITH
 THE STORAGE AREA THE OCCUPANT LOAD OF THE KITCHEN WOULD
 BE 6 PLUS THE SERVERS.
  
 2L) THE EXIT FROM THE KITCHEN ITSELF IS NOT AN
 ACCESSIBLE MEANS OF EGRESS. 2014 FBC-ACCESSIBILITY
 CODE. 206.4.1 PUBLIC ENTRANCES. (DOORWAYS) IN ADDITION
 TO ENTRANCES REQUIRED BY 206.4.2 THROUGH 206.4.9, AT
 LEAST 60 PERCENT OF ALL PUBLIC ENTRANCES SHALL COMPLY
 WITH 404. 2 X 0.60= 1.2 OR 2 MEANS OF ACCESSIBLE
 ENTRANCES / EXITS.
  
 2M) THE DOOR THAT LEADS INTO THE KITCHEN DOES NOT HAVE
 THE 18 INCHES CLEARANCE ON THE LATCH SIDE OF THE DOOR.
 ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES. DOORS.
 MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL
 COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL
 EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED
 LATCH SIDE FOR SIDE CLEARANCE.
  
 2N) THE LIFE SAFETY SHEET DOES NOT SHOW COMPLIANCE WITH
 THE 2014 FBC-ACCESSIBILITY CODE;
 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
 TOTAL SEATING 84 X 0.05 = 4.2, ROUND UP TO 5.
  
 2O) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 2P) 206.2.5 RESTAURANTS AND CAFETERIAS. IN RESTAURANTS
 AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL BE PROVIDED
 TO ALL DINING AREAS, INCLUDING RAISED OR SUNKEN DINING
 AREAS, AND OUTDOOR DINING AREAS.
  
 2R) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS.
  
 2R)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 2R)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3) PLEASE NOTE UNDER THE ADDRESS OF 123 DATURA NOR 125
 DATURA DOES THE CITY RECORDS SHOW A WALK IN COOLER/
 FREEZER PLEASE PROVIDE PERMIT FOR WORK? 107.2.1.3
  
 4A) THE M-2 SHEET SHOWS AN A/C STAND, IS THIS A GENERIC
 DETAIL OR IS THERE GOING TO BE A ACTUAL A/C STAND
 INSTALLED ON THE ROOF? IF SO SHOW COMPLIANCE WITH:
 2014 / 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(G) PRE-ENGINEERED A/C STANDS
  
 4B) THE ROOF TOP A/C STAND SUBMIT A PRODUCT APPROVAL
 REPORT. PLEASE IDENTIFY THE FOLLOWING REQUIREMENTS
 CALCULATING THE AREA (SIDE VIEW) OF THE ROOF TOP
 COMPRESSORS, CONFIGURATION ON STAND, THE MEAN ROOF
 HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT, CIRCLED
 THE DESIGN PARAMETERS IN THE TABLES, ANCHORS AND UPLIFT
 VERSES MOMENT FOR THE UNIT TO THE STAND AND THE STAND
 TO THE ROOF. THE PRODUCT APPROVAL IS TO BE REVIEWED BY
 THE DESIGNER OF RECORD, APPROVED BEFORE SUBMISSION TO
 THE BUILDING DEPARTMENT.
  
 4C) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4D) PLEASE ALSO PROVIDE THE WIND DESIGN CRITERIA. 2014
 FBC-B 1603.1.4 WIND DESIGN DATA.
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  