Plan Review Notes
Plan Review Notes For Permit 17110117
Permit Number 17110117
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-11-08 12:15:10THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE IS NO EXISTING OR PROPOSED OCCUPANCY
 CLASSIFICATION PER THE FLORIDA FIRE PREVENTION CODE.
  
 PLEASE PROVIDE THE PROPOSED OCCUPANCY CLASSIFICATION
 INCLUDING OCCUPANY CODE.
  
  
  
 2) THE IS NO NOTE INDICATING COMPLAINCE WITH ANY LIFE
 SAFETY CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
  
  
 3) THERE IN NO INDICATION OF ANY EXISTING OR PROPOSED
 BUILDING INFORMATION. I.E. TYPE OF CONSTRUCTION, FIRE
 SPRINKLER, FIRE ALARM, INTEIOR FINISHES, ETC.
  
 PLEASE PROVIDE DETAILS.
  
  
  
 4) THERE ARE NO DIMENSIONS INDICATED.
  
 PLEASE PROVIDE ALL DIMENSIONS OF EACH
 AREA/ROOM/SPACE/CORRIDOR, ETC.
  
  
  
 5) THE IS NO DOOR SCHEDULE.
  
 PLEASE PROVIDE DOOR DETAILS, INCLUDING, TYPE, SIZE,
 LOCKS, LATCHES, HARDWARE, ETC.
  
  
  
 6) A KITCHEN IS INDICATED. THERE IS NO INFORMATION
 REGARDING COMPLIANCE WITH NFPA 96, STANDARD FOR
 VENTILATION CONTROL AND FIRE PROTECTION OF COMMERCIAL
 COOKING OPERATIONS, 2011 EDITION, EITHER EXISITNG OR
 PROPOSED.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF COMPLIANT EXISITNG
 OR PROPOSED SHOP DRAWINGS UNDER SEPARATE PERMIT.
  
  
  
 7) A PIZZA OVEN IS INDICATED. THERE ARE NO
 SPECIFICATION SHEETS OF PROPTECTION PER NFPA 96.
  
 PLEASE PROVIDE MANUFACTURES DETAIL SHEETS INCLUDING
 INSTALLATION INSTURCTIONS.
  
  
  
 8) THERE IS ONLY ONE EXIT FROM THE MAIN AREA AND TWO
 ARE REQUIRED. THE EXIT FROM THE MAIN AREA CAN NOT PASS
 THRU THE KITCHEN AREA.
  
 PLEASE CORRECT OR PROVIDE FFPC REFERENCE FOR THE
 EXCEPTION.
  
  
  
 9) THE DOOR TO THE FRONT RESTROOM APPEARS TO OPEN UP
 INTO THE EXIT CORRIDOR/PATHWAY.
  
 PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY
 OPEN.
  
 PLEASE CORRECT OR JUSTIFY PER THE CODE.
  
  
  
 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved