2017-11-21 08:23:22 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR |
| PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM |
| BONDING TERMINATION POINT. NEC 215.5, 230, 250.50, |
| 250.94, 408.30 |
| 2. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| IS ADEQUATE. NEC 215.2, 220, 408.30 |
| 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| WITH CODE. NEC 210.8, 210.12, 215.5, 408.4 |
| 4. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER |
| ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE |
| CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH |
| CODE. FBC CE 405.5 |
| 5. OCCUPANCY SENSORS FOR BATHROOMS SHOULD BE INSIDE |
| BATHROOMS. PROVIDE CORRECTION. FBC 107.2.1; FBC CE |
| 405.2 |
| 6. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED |
| IN THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE |
| AUTOMATIC CONTROL REQUIRED. FBC CE 405.2.2, 405.2.2.2 |
| 7. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED |
| SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| SUBMITTALS WHERE APPLICABLE FOR LOW VOLTAGE SYSTEMS, |
| FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS, |
| WALK-IN COOLERS, HOODS, ETC. FBC 105.1, 107.2.1 |
| 8. PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT |
| CURRENT AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE. |
| NEC 110.10 |
| 9. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| 10. PROVIDE AIC RATING OF PANELS. NEC 110.3, 110.9 |
| 11. ALL RECEPTACLE OUTLETS IN KITCHEN AND BAR AREAS ARE |
| REQUIRED TO BE GFCI PROTECTED. PROVIDE CORRECTION. NEC |
| 210.8 |
| 12. PROVIDE AUTOMATIC CONTROL FOR SIGN AND SHOW WINDOW |
| LIGHTING. LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN |
| OPERATION SHALL BE CONTROLLED BY EITHER A COMBINATION |
| OF A PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL |
| TIME SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN |
| OPERATION SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME |
| SWITCH OR PHOTOSENSOR. ALL TIME SWITCHES SHALL BE |
| CAPABLE OF RETAINING PROGRAMMING AND THE TIME SETTING |
| DURING LOSS OF POWER FOR A PERIOD OF AT LEAST 10 HOURS. |
| FBC CE 405.2.4 |
| |
| A FULL REVIEW WAS NOT POSSIBLE AT THIS TIME DUE TO A |
| LACK OF INFORMATION ON THE PLANS. FURTHER REVIEW |
| COMMENTS MAY BE NECESSARY. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |