2017-11-21 08:23:22CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR
 PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM
 BONDING TERMINATION POINT. NEC 215.5, 230, 250.50,
 250.94, 408.30
 2. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30
 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4
 4. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER
 ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE
 CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH
 CODE. FBC CE 405.5
 5. OCCUPANCY SENSORS FOR BATHROOMS SHOULD BE INSIDE
 BATHROOMS. PROVIDE CORRECTION. FBC 107.2.1; FBC CE
 405.2
 6. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED
 IN THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE
 AUTOMATIC CONTROL REQUIRED. FBC CE 405.2.2, 405.2.2.2
 7. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS WHERE APPLICABLE FOR LOW VOLTAGE SYSTEMS,
 FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS,
 WALK-IN COOLERS, HOODS, ETC. FBC 105.1, 107.2.1
 8. PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT
 CURRENT AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE.
 NEC 110.10
 9. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 10. PROVIDE AIC RATING OF PANELS. NEC 110.3, 110.9
 11. ALL RECEPTACLE OUTLETS IN KITCHEN AND BAR AREAS ARE
 REQUIRED TO BE GFCI PROTECTED. PROVIDE CORRECTION. NEC
 210.8
 12. PROVIDE AUTOMATIC CONTROL FOR SIGN AND SHOW WINDOW
 LIGHTING. LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN
 OPERATION SHALL BE CONTROLLED BY EITHER A COMBINATION
 OF A PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL
 TIME SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN
 OPERATION SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME
 SWITCH OR PHOTOSENSOR. ALL TIME SWITCHES SHALL BE
 CAPABLE OF RETAINING PROGRAMMING AND THE TIME SETTING
 DURING LOSS OF POWER FOR A PERIOD OF AT LEAST 10 HOURS.
 FBC CE 405.2.4
  
 A FULL REVIEW WAS NOT POSSIBLE AT THIS TIME DUE TO A
 LACK OF INFORMATION ON THE PLANS. FURTHER REVIEW
 COMMENTS MAY BE NECESSARY.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER