2017-11-14 10:45:06ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6667 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION
  
 1. THE PLANS SUBMITTED DO NOT CLEARLY SHOW EXISTING
 AREAS AND AREAS OF NEW WORK.
  
 1A. THE LIFE SAFETY PLAN SHOWS NEW WALLS AROUND THE
 KITCHEN AREA BUT ARE NOT SHOWN ON A1.0, E1 OR P1.
  
 1B. NO WALL DETAIL OR DOOR SCHEDULE PROVIDED.
  
 1C. PLANS DO NOT HAVE DIMENSIONS SHOWN.
  
 INSUFFICIENT INFORMATION SUBMITTED FOR PLAN REVIEW.
 SUBMIT PLANS SHOWING THE LOCATIONS AND TYPE OF WORK TO
 BE COMPLETED.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 2. EXIT ACCESS SHOWN IS GOING THROUGH KITCHEN AREA.
  
 FBC 1014.2, FBC 107.2.3 EGRESS THROUGH INTERVENING
 SPACES. EGRESS THROUGH INTERVENING SPACES SHALL COMPLY
 WITH THIS SECTION. 4. EGRESS SHALL NOT PASS THROUGH
 KITCHENS, STORAGE ROOMS, CLOSETS OR SPACES USED FOR
 SIMILAR PURPOSES.
  
 3. DOORS ON ACCESSIBLE ROUTES. FRONT DOOR SHALL COMPLY
 WITH THE FOLLOWING SECTION FOR RECESSED DOORS.
  
 FBC ACCESSIBILITY 404.2.4.3 RECESSED DOORS AND GATES.
  
 MANEUVERING CLEARANCES FOR FORWARD APPROACH SHALL BE
 PROVIDED WHEN ANY OBSTRUCTION WITHIN 18 INCHES (455 MM)
 OF THE LATCH SIDE OF A DOORWAY PROJECTS MORE THAN 8
 INCHES (205 MM) BEYOND THE FACE OF THE DOOR, MEASURED
 PERPENDICULAR TO THE FACE OF THE DOOR OR GATE.
 REAR DOOR SHALL COMPLY WITH FBC ACCESSIBILITY 404.2.4
 MANEUVERING CLEARANCES.
 MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL
 COMPLY WITH FBC ACCESSIBILITY 404.2.4. MANEUVERING
 CLEARANCES SHALL EXTEND THE FULL WIDTH OF THE DOORWAY
 AND THE REQUIRED LATCH SIDE OR HINGE SIDE CLEARANCE.
  
 FBC ACCESSIBILITY 404.2.4.1 SWINGING DOORS AND GATES.
 SWINGING DOORS AND GATES SHALL HAVE MANEUVERING
 CLEARANCES COMPLYING WITH TABLE 404.2.4.1. SEE DETAIL
 (C).
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  
  