Plan Review Notes
Plan Review Notes For Permit 17110114
Permit Number 17110114
Review Stop M
Sequence Number 2
Notes
Date Text
2017-11-30 14:31:412ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17100499
 11/30/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE DESIGNER OF RECORD LILLIAN GONZALEZ P.E. MUST
 PROVIDE HER RAISED OR INK SEAL AND SIGNATURE ON THE
 MECHANICAL PLAN- SECTION 61G15-23.002 FLORIDA
 ADMINISTRATIVE CODE.
  
 2) AS PREVIOUSLY NOTED IN THE FIRST REVIEW, THE RETURN
 TRANSFER DUCTS FROM THE BEDROOM ARE UNDERSIZED PER
 SECTION
  
 3) THE SUBMITTED INSTALLATION INSTRUCTIONS FOR THE
 CONDENSER TIE-DOWN CLIPS ARE INCOMPLETE WITHOUT THE
 FRONT COVER SHEET OF THE MIAMI-DADE NOA OR FLORIDA
 PRODUCT APPROVAL- RULE 9N-3.
  
 4) THE OWNER/AGENT'S SIGNATURE AND DATE ARE REQUIRED ON
 PAGE 1 OF ENERGY FORM R405.
  