Plan Review Notes
Plan Review Notes For Permit 17110114
Permit Number 17110114
Review Stop M
Sequence Number 1
Notes
Date Text
2017-11-08 13:25:491ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL , ENERGY
 CONSERVATION CODES
 PERMIT #17110114
 11/8/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PALM BEACH COUNTY APPRAISERS REPORT INDICATES
 THE RESIDENCE HAS NEVER HAD AN AC SYSTEM, AND THERE IS
 NO RECORD OF A PERMIT FOR A SYSTEM IN THE CITY PERMIT
 FILES. PLEASE REFER TO SECTION R101.4.5 FBC-14 ENERGY
 CONSERVATION AND SUBMIT AN ENERGY EFFICIENCY COMPLIANCE
 REPORT FOR THE NEWLY CONDITIONED RESIDENCE.
  
 2) THE RETURN AIR TRANSFER DUCTS FROM THE BEDROOMS ARE
 UNDERSIZED PER SECTION M1602.4 FBC-14 RESIDENTIAL.
  
 3) PROVIDE ENGINEERING FOR TIE DOWN OF THE RTU-SECTION
 301.15.
  
 4) PROVIDE AN ELECTRICAL PLAN AND A SUB-PERMIT
 APPLICATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  