Plan Review Notes For Permit 17110080 |
Permit Number |
17110080 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-11-02 18:11:32 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. FBC 107, PROVIDE A GRAPHIC OF THE PROPOSED FASTENING | | (OR REVISE FASTENING). | | | | ENGINEER HAS SPECIFIED: | | ". . . BASE SHEET BE SECURED 2 ROWS AT 6" O.C. AT THE | | LAP . . ." (ETC.) | | | | IT IS NOT CLEAR HOW THE CONTRACTOR WILL BE ABLE TO | | INSTALL TWO ROWS 6" O.C. IN A 4" LAP. THE LANGUAGE | | DIFFERS FROM THE SECOND PAGE WHICH SPECIFIES ONE ROW. | | | | 2. ENGINEER ALSO SPECIFIES: | | "AT THE PERIMETER FOR 4' IN EACH DIRECTION . . . " | | | | 3. SEE CALCULATIONS; PER RAS117 10.4.5, FOR FRACTIONS | | ROUND DOWN. (NOTE THAT MINIMUM SPACING IS 4"). | | | | | | | | IT IS NOT CLEAR WHAT "EACH DIRECTION" MEANS RELATIVE TO | | THE PERIMETER. |
|