2017-11-16 09:08:06FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER
 CIRCUIT OR BRANCH CIRCUIT SUPPLYING A
 SIGN OR OUT-LINE LIGHTING SYSTEM, SHALL BE CONTROLLED
 BY AN EXTERNALLY OPERABLE SWITCH
 OR CIRCUIT BREAKER THAT WILL OPEN ALL UNGROUNDED
 CONDUCTORS WITHIN SIGHT OF THE SIGN
 NEC 600.6(A)(1)
  
 YOU HAVE A DISCONNECT ON THE ROOF BUT NOT AT THE SIGN.
  
 ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 405.1 SHALL
 HAVE AUTOMATIC CONTROLS TO TURN
 OFF AT DAYLIGHT OR WHEN NOT REQUIRED. CONTROLS SHALL BE
 PHOTOSENSOR & TIME CLOCK OR
 ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES SHALL BE
 CAPABLE OF RETAINING PROGRAMING
 DURING A LOSS OF POWER FOR A MINIMUM OF 10 HOURS.
 FBC-EC 405.2.4