2018-01-10 12:10:43 | 2ND REVIEW: FBC 2014 5TH EDITION |
| |
| PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED |
| |
| 2ND REQUEST 1. PLEASE SHOW CLEAR FLOOR SPACE FOR THE |
| TOILET, URINAL AND LAVATORY. PER FBC ACC 604.3.1, 605.3 |
| AND 606.2 SHT. A2.1 DOES NOT SHOW THE CLEAR FLOOR SPACE |
| FOR THE TOILET AND URINAL. |
| |
| 2ND REQUEST 2. PLEASE SHOW COMPLIANCE WITH FBC ACC |
| 603.3 MIRRORS. |
| MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALLL |
| BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES |
| OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE |
| OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM |
| ABOVE THE FINISH FLOOR OR GROUND. |
| A) DETAILS #3, #4, #7 SHOWS A DIMENSION OF 6-3/4" FROM |
| THE TOP OF THE LAVATORY TO THE BOTTOM OF THE MIRROR |
| WHICH MAKES THE TOTAL DIMENSION FROM FINISHED FLOOR TO |
| THE BOTTOM OF THE MIRROR 40-3/4" THE CODE REQUIRES 40" |
| EXACTLY 3/4" IS TO MUCH TO ALLOW FOR A TOLERANCE PLEASE |
| CORRECT THE DIMENSION SO THAT IT MEETS THE CODE |
| REQUIREMENT. |
| B) DETAIL #5 SOMEONE CHANGED THE IN PEN THE MIN 40" TO |
| MAX ON THE DOUBLE LAVATORY BUT THEY DID NOT CHANGE |
| IT-ON THE SINGLE LAVATORY IN-THE ACCESSIBLE STALL |
| |
| 2ND REQUEST 3. PLEASE SHOW COMPLIANCE WITH FBC ACC |
| 609.4 POSITION OF GRAB BARS. |
| GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, |
| 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE THE |
| FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING |
| SURFACE. PLEASE SHOW THE GRAB BARS MEASURED TO THE TOP |
| OF THE GRIPPING SURFACE. |
| |
| 2ND REQUEST 4. PLEASE SHOW COMPLIANCE WITH FBC ACC |
| 604.7 DISPENSERS. |
| TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT |
| OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| DISPENSER. SHOW DIMENSION ON PLAN |
| |
| 2ND REQUEST 5. PLEASE SHOW COMPLIANCE WITH FBC ACC |
| 604.5.1 SIDE WALL. |
| THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG MINIMUM, |
| LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE REAR WALL |
| AND EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL. |
| |
| 2ND REQUEST 6. SHT. A2.1 DETAIL #8 SHOWS LAVATORY RIM |
| AT 36" OF FINISH FLOOR IT SHALL BE 34". PER FBC ACC |
| 606.3 |
| |
| 2ND REQUEST 10. THE WATER FILTER SHOWN ON SHT. K 2.0 |
| DETAIL P.1 IS NOT SHOWN ON WATER PIPE RISER PLEASE |
| CLARIFY. PER WPB AMEND TO FBC 107.2.1 EVEN IF IT IS |
| EXISTING PLEASE SHOW ON WATER AND SANITARY RISER |
| DIAGRAM AND MARK AS EXISTING. |
| |
| 2ND REQUEST 11. A BACKFLOW IS REQUIRED ON SUPPLY TO ICE |
| MACHINE WATER FILTER AND BEVERAGE DISPENSERS AND COFFEE |
| MACHINES. PER FBC PL 608.3, 608.16.1 AND 608.16.10 |
| BACKFLOWS ARE NOT SHOWN ON THE WATER RISER AND ON THE |
| PLUMBING FIXTURE SCHEDULE IT REFERS TO NOTE 23 I COULD |
| NOT LOCATE NOTE 23 ON PLAN SHEET. |
| |
| 2ND REQUEST 12. ONLY FIXTURES THAT PRODUCE GREASE WASTE |
| SHALL DISCHARGE THROUGH A GREASE INTERCEPTOR LIKE |
| KITCHEN AND FOOD PREP AREA AND MOP SIN, THE FIXTURES IN |
| BAR AREA SHALL NOT DISCHARGE THROUGH THE GREASE |
| INTERCEPTOR. PER FBC PL 1003.2 THE BARS FIXTURE ARE |
| STILL SHOWN ON GREASE WASTE RISER. |
| |
| 2ND REQUEST 13. LAVATORY'S SHALL COMPLY WITH FBC PL |
| 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING |
| FACILITIES. |
| TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND |
| GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES |
| PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED |
| WATER SHALL BE DELIVERED THROUGH AN APPROVED |
| WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| 1070 OR CSA B125.3. NOT SHOWN ON PLAN PLEASE PROVIDE |
| NOTE |
| |
| 2ND REQUEST 14. P;LEASE SHOW ICE MACHINE ON WATER |
| RISER. PER WPB AMEND TO FBC 107.2.1 NOT SHOW ON RISER |
| EVEN IF IT IS EXISTING PLEASE SHOW ON WATER AND |
| SANITARY RISER DIAGRAM AND MARK AS EXISTING. |
| |
| 2ND REQUEST 15. THE FIXTURE COUNT SHAL COMPLY WITH FBC |
| PL 403.1.3 POTTY PARITY. |
| IN ASSEMBLY OCCUPANCIES, RESTROOMS WHICH ARE OPEN TO |
| THE PUBLIC MUST HAVE A RATIO OF 3:2 WATER CLOSETS |
| PROVIDED FOR WOMEN AS THE COMBINED TOTAL OF WATER |
| CLOSETS AND URINALS PROVIDED FOR MEN, UNLESS THESE ARE |
| TWO OR FEWER SUCH FIXTURES FOR MEN, IN ACCORDANCE WITH |
| SECTION 553.86, FLORIDA STATUTES. |
| IN ORDER TO COMPLY WITH THIS CODE SEC THERE SHALL BE |
| THE SAME NUMBER OF TOILETS IN THE WOMENS BATHROOM AS |
| THE COMBINED NUMBERS OF TOILETS AND URINALS IN THE |
| MENS. |
| |
| |
| 2ND REQUEST 16. A TEST PORT IS REQUIRED ON THE |
| DISCHARGE OF GREASE INTERCEPTOR. PER WPB UTILITIES. THE |
| DETAIL DOES NOT COMPLY A DOUBLE SANITARY TEE WITH A CAP |
| ON THE BOTTOM SHALL NOT BE USED. A MIN 4" TWOWAY CLEAN |
| OUT OR PREMANUFACTERED TEST PORT SHALL BE USED PER WPB |
| UTILITIES. |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |