2017-11-21 12:11:461ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW CLEAR FLOOR SPACE FOR THE TOILET, URINAL
 AND LAVATORY. PER FBC ACC 604.3.1, 605.3 AND 606.2
  
 2. PLEASE SHOW COMPLIANCE WITH FBC ACC 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALLL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 3. PLEASE SHOW COMPLIANCE WITH FBC ACC 609.4 POSITION
 OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE.
  
 4. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.7
 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER.
  
 5. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.5.1 SIDE
 WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG MINIMUM,
 LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE REAR WALL
 AND EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL.
  
 6. SHT. A2.1 DETAIL 8 AND 5 SHOWS LAVATORY RIM AT 35"
 OF FINISH FLOOR IT SHALL BE 34". PER FBC ACC 606.3
  
 7. PLEASE LIST APPLICABLE CODES. PER WPB AMEND TO FBC
 107.2.1
  
 8. PLEASE PROVIDE A BREAK DOWN OF OCCUPANT LOAD. PER
 WPB AMEND TO FBC 107.2.1
  
 9. HOT WATER SYSTEM SHALL COMPLY WITH FBC PL 607.2 HOT
 OR TEMPERED WATER SUPPLY TO FIXTURES.
 THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING,
 FROM THE SOURCE OF HOT WATER TO THE FIXTURES THAT
 REQUIRE HOT OR TEMPERED WATER, SHALL NOT EXCEED 50 FEET
 . RECIRCULATING SYSTEM PIPING AND HEAT-TRACED PIPING
 SHALL BE CONSIDERED TO BE SOURCES OF HOT OR TEMPERED
 WATER.
  
 10. THE WATER FILTER SHOWN ON SHT. K 2.0 DETAIL P.1 IS
 NOT SHOWN ON WATER PIPE RISER PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 11. A BACKFLOW IS REQUIRED ON SUPPLY TO ICE MACHINE
 WATER FILTER AND BEVERAGE DISPENSERS AND COFFEE
 MACHINES. PER FBC PL 608.3, 608.16.1 AND 608.16.10
  
 12. ONLY FIXTURES THAT PRODUCE GREASEY WASTE SHALL
 DISCHARGE THROUGH A GREASE INTERCEPTOR LIKE KITCHEN AND
 FOOD PREP AREA AND MOP SIN, THE FIXTURES IN BAR AREA
 SHALL NOT DISCHARGE THROUGH THE GREASE INTERCEPTOR. PER
 FBC PL 1003.2
  
 13. LAVATORY'S SHALL COMPLY WITH FBC PL 416.5 TEMPERED
 WATER FOR PUBLIC HAND-WASHING FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
  
 14. P;LEASE SHOW ICE MACHINE ON WATER RISER. PER WPB
 AMEND TO FBC 107.2.1
  
 15. THE FIXTURE COUNT SHAL COMPLY WITH FBC PL 403.1.3
 POTTY PARITY.
 IN ASSEMBLY OCCUPANCIES, RESTROOMS WHICH ARE OPEN TO
 THE PUBLIC MUST HAVE A RATIO OF 3:2 WATER CLOSETS
 PROVIDED FOR WOMEN AS THE COMBINED TOTAL OF WATER
 CLOSETS AND URINALS PROVIDED FOR MEN, UNLESS THESE ARE
 TWO OR FEWER SUCH FIXTURES FOR MEN, IN ACCORDANCE WITH
 SECTION 553.86, FLORIDA STATUTES.
  
 EXCEPTION: THIS SECTION DOES NOT APPLY TO
 ESTABLISHMENTS LICENSED UNDER CHAPTER 509, FLORIDA
 STATUTES, IF THE ESTABLISHMENT DOES NOT PROVIDE MEETING
 OR BANQUET ROOMS WHICH ACCOMMODATE MORE THAN 150
 PEOPLE, AND THE ESTABLISHMENT HAS AT LEAST THE SAME
 NUMBER OF WATER CLOSETS FOR WOMEN AS THE COMBINED TOTAL
 OF WATER CLOSETS AND URINALS FOR MEN.
  
  
 16. A TEST PORT IS REQUIRED ON THE DISCHARGE OF GREASE
 INTERCEPTOR. PER WPB UTILITIES
  
 17. PLEASE PROVIDE SIZING CALCULATIONS FOR THE GREAS
 INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1
  
 18. WATER SYSTEM SHALL COMPLY WITH FBC PL 604.9 WATER
 HAMMER.
 THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM
 SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER
 HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED
 WHERE QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER
 ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S INSTRUCTIONS. WATER-HAMMER ARRESTORS
 SHALL CONFORM TO ASSE 1010.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  