Date |
Text |
2017-11-21 12:29:34 | 1ST REVIEW: FBC 2014 5TH EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL |
| CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER |
| FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2. |
| |
| 2. PLEASE SHOW THE SYSTEM PRESSURE ON THE RISER. PER |
| WPB AMEND TO FBC 107.2.1 |
| |
| 3. PLEASE INDICATE TYPE OF PIPE ON THE RISER. PER WPB |
| AMEND TO FBC 107.2.1 |
| |
| 4. PLEASE PROVIDE ACCURATE SIZING TABLE THE SHOWN ON |
| PLAN IS INCORRECT TABLE 402.4(3) IS SHOWN AS 2PSI ON |
| THE PLAN IT IS LESS THAN 2PSI IN THE FBC FG TABLE |
| 402.4(3) |
| |
| 5. PLEASE PROVIDE LENGTH FROM METER TO FURTHEST |
| APPLIANCE NOT SHOWN ON RISER. FBC FG 402.4.1. |
| |
| 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE |
| FBC-2014 FUEL GAS CODE SEC. 304. |
| |
| 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL |
| GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA |
| 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 |
| |
| 10. THE MAX DISTANCE IS SHOWN AS 40' IS THAT FROM METER |
| TO THE METER TO FIRST REG OF FROM REG TO FURTHEST |
| APPLIANCE PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| |
| 11. PLEASE SHOW DRIP LEGS ON RISER DIAGRAM. PER WPB |
| AMEND TO FBC 107.2.1 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561-805-6711 |
| [email protected] |
| |