2017-11-16 14:54:12 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED |
| SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| SUBMITTALS WHERE APPLICABLE FOR LOW VOLTAGE SYSTEMS, |
| FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS, |
| WALK-IN COOLERS, HOODS, ETC. FBC 105.1, 107.2.1 |
| 2. EXISTING RISER AND PROPOSED RISER ARE BOTH MISSING |
| INFORMATION. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS |
| OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR |
| PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM |
| BONDING TERMINATION POINT. NEC 215.5, 230, 250.50, |
| 250.94, 408.30 |
| 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| IS ADEQUATE. NEC 215.2, 220, 408.30 |
| 4. PROVIDE AIC RATING OF SERVICE DISCONNECTS AND |
| PANELS. NEC 110.3, 110.9 |
| 5. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| NEC 110.9, 110.10 |
| 6. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED |
| IN THE FBC ENERGY CODE. KITCHEN AND BAR AREAS DO NOT |
| SHOW THE AUTOMATIC CONTROL REQUIRED. FBC CE 405.2.2, |
| 405.2.2.2 |
| 7. INSIDE THE PANEL B PANEL SCHEDULE IS A LOAD |
| CALCULATION LABELED "PANEL A". IS THIS A TYPO? CLARIFY |
| AND/OR CORRECT. FBC 107.2.1 |
| 8. THERE IS A NOTE THAT STATES ALL KITCHEN AND BAR AREA |
| RECEPTACLES SHALL BE GFCI PROTECTED, EXCEPT THOSE FOR |
| EQUIPMENT. ALL RECEPTACLE OUTLETS ARE REQUIRED TO HAVE |
| GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8 |
| 9. PROVIDE DETAILS OF THE METHOD OF SHUTDOWN FOR THE |
| ELECTRICAL RECEPTACLE OUTLETS LOCATED UNDER THE HOOD |
| PER NFPA 96. NFPA 96, SECTION 10.4.1, FBC 107.2.1 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |