2017-11-06 13:33:14 | 2014 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17101215 |
| ADD: 1020 11TH. ST. |
| CONT: T. B. D. / TO BE DETERMINED |
| TEL: 561-822-1437 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. NOV. 06/ 2017 |
| ACTION: DENIED |
| |
| 1) THE COVERSHEET A0.0 LIST THE BUILDING CONSTRUCTION |
| TYPE AND INDICATES THE AMERICAN LEGION MEETS THERE, AND |
| THE BUILDING IS OWNED BY THE CITY OF WEST PALM BEACH |
| (TITLE II). WHAT THE DESIGNER OF RECORD HAS NOT |
| DECLARED IS THE OCCUPANCY, THIS MAY BE A MIXED USE |
| BUILDING DEPENDING ON THE FUNCTION OF THE BUILDING, A |
| BANQUET HALL WITH TABLE AND CHAIRS, USED FOR MEETINGS |
| WITH CHAIRS ONLY AND OR AS A DANCE HALL OR EVENT HALL |
| WITH A MIXTURE OF ALL THREE. PLEASE PROVIDE AN |
| OCCUPANCY TYPE. |
| |
| 2014 FBC-B SECTION 302.1. STRUCTURES OR PORTIONS OF |
| STRUCTURES SHALL BE CLASSIFIED WITH RESPECT TO |
| OCCUPANCY IN ONE OR MORE OF THE GROUPS LISTED IN THIS |
| SECTION. A ROOM OR SPACE THAT IS INTENDED TO BE |
| OCCUPIED AT DIFFERENT TIMES FOR DIFFERENT PURPOSES |
| SHALL COMPLY WITH ALL OF THE REQUIREMENTS THAT ARE |
| APPLICABLE TO EACH OF THE PURPOSES FOR WHICH THE ROOM |
| OR SPACE WILL BE OCCUPIED. STRUCTURES WITH MULTIPLE |
| OCCUPANCIES OR USES SHALL COMPLY WITH SECTION 508. |
| |
| 2) SHEET A2.0 PROVIDES A TABLE LISTING THE SQUARE FOOT |
| AREA OF THE ROOMS BUT DOES NOT PROVIDE THE OCCUPANT |
| LOAD FOR THE ROOMS AND OVERALL TOTAL OCCUPANT LOAD. |
| OCCUPANT LOADS TO BE USED IN : |
| |
| TABLE 1004.1.2 OF THE 2014 FBC-B. A ROOM OR SPACE THAT |
| IS INTENDED TO BE OCCUPIED AT DIFFERENT TIMES FOR |
| DIFFERENT PURPOSES SHALL COMPLY WITH ALL OF THE |
| REQUIREMENTS THAT ARE APPLICABLE TO EACH OF THE |
| PURPOSES FOR WHICH THE ROOM OR SPACE WILL BE OCCUPIED |
| THE MOST RESTRICTIVE WOULD APPLY. |
| |
| 2014 FBC-B 201, FLOOR AREA, NET. THE ACTUAL OCCUPIED |
| AREA NOT INCLUDING UNOCCUPIED ACCESSORY AREAS SUCH AS |
| CORRIDORS, STAIRWAYS, TOILET ROOMS, MECHANICAL ROOMS |
| AND CLOSETS. |
| |
| FLOOR AREA, GROSS. THE FLOOR AREA WITHIN THE INSIDE |
| PERIMETER OF THE EXTERIOR WALLS OF THE BUILDING UNDER |
| CONSIDERATION, EXCLUSIVE OF VENT SHAFTS AND COURTS, |
| WITHOUT DEDUCTION FOR CORRIDORS, STAIRWAYS, CLOSETS, |
| THE THICKNESS OF INTERIOR WALLS, COLUMNS OR OTHER |
| FEATURES. THE FLOOR AREA OF A BUILDING, OR PORTION |
| THEREOF, NOT PROVIDED WITH SURROUNDING EXTERIOR WALLS |
| SHALL BE THE USABLE AREA UNDER THE HORIZONTAL |
| PROJECTION OF THE ROOF OR FLOOR ABOVE. THE GROSS FLOOR |
| AREA SHALL NOT INCLUDE SHAFTS WITH NO OPENINGS OR |
| INTERIOR COURTS. |
| |
| 3) SHEET A2.0 SHOWS PROPOSED WORK IN BOTH THE MENS & |
| WOMENS RESTROOMS. THE COVERSHEET INDICATES A LEVEL 2 |
| ALTERATION. 2014 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. ALSO UNDER THE |
| LEVEL II ALTERATIONS OF THE 2014 EXISTING BUILDING CODE |
| SECTION 806.1 A BUILDING, FACILITY, OR ELEMENT THAT HAS |
| IS ALTERED SHALL COMPLY WITH THE PROVISIONS OF THE |
| FLORIDA BUILDING CODE, ACCESSIBILITY. PLEASE NOTE THE |
| NEW LAYOUT OF BOTH THE MENS AND WOMENS RESTROOMS DOES |
| NOT COMPLY WITH THE ACCESSIBILITY CODE 604.3.1 SIZE, |
| 604.3.2 OVERLAP NOR 604.8.1.6. |
| |
| 4) SHEET A2.1 DETAILS IN BOTH THE MENS AND WOMENS |
| RESTROOMS THE MIRRORS ARE SHOWN ABOVE THE MAXIMUM |
| HEIGHT OF 40 INCHES TO THE BOTTOM EDGE OF THE |
| REFLECTIVE MIRROR SURFACE. ACCESS. CODE 603.3. |
| |
| 5) WHEN THE OCCUPANCY CLASSIFICATION IS GIVEN AND THE |
| OCCUPANT LOAD IS KNOWN PLEASE REVIEW SECTION 810.1 OF |
| THE EXISTING BUILDING CODE TO SEE IF THE FIXTURE COUNT |
| HAS BEEN MET. |
| |
| 6) SHEET A2.0 ALSO SHOWS WORK AT THE BAR AREA. SHEET |
| A2.2 DETAIL # 10 SHOWS THE BAR TOP AT A HEIGHT OF 3?-6? |
| OR 42 INCHES TALL. PLEASE SHOW A PORTION OF THE BAR |
| MEETING THE ACCESSIBILITY CODE 226.1 WHERE DINING |
| SURFACES ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR |
| DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES AND |
| STANDING SPACES AT THE DINING SURFACES SHALL COMPLY |
| WITH 902. 902.1 .DINING SURFACES AND WORK SURFACES |
| SHALL COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 |
| GENERAL. DINING SURFACES INCLUDE, BUT ARE NOT LIMITED |
| TO, BARS, TABLES, LUNCH COUNTERS, AND BOOTHS. |
| |
| 6)(A) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR |
| SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD |
| APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE |
| COMPLYING WITH 306 SHALL BE PROVIDED. |
| |
| 6)(B) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND |
| WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES |
| MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| |
| 7) SHEET A2.2 SHOWS A NEW EXHAUST HOOD. HOOD AND |
| SUPPRESSION ARE REVIEWED UNDER SEPARATE PERMITS. |
| 2801.1 SCOPE. |
| MECHANICAL APPLIANCES, EQUIPMENT AND SYSTEMS SHALL BE |
| CONSTRUCTED, INSTALLED AND MAINTAINED IN ACCORDANCE |
| WITH THE FLORIDA BUILDING CODE, MECHANICAL AND THE |
| FLORIDA BUILDING CODE, FUEL GAS. |
| |
| 8) SHEET S1.0 THE DESIGN PRESSURES FOR THE COMPONENTS |
| AND CLADDING ARE LOW AND THE SAME FOR 10SQ. FT. 20 SQ. |
| FT. AND 30 SQ. FT. 2014 FBC-B TABLE 1609.6.2. & TABLE |
| R301.2(2). UNTIL THE PRESSURES ARE CORRECTED THE |
| PRODUCT APPROVALS CANNOT BE EVALUATED. |
| |
| 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |