Date |
Text |
2017-11-01 08:46:50 | 2014 FBC- BUILDING PLAN REVIEW |
| W. P. B. REVISION: 17101200 |
| W. P. B. PERMIT: 17040865 |
| ADD: 101 N. CLEMATIS ST. SUITE: 110 |
| CONT: HITT CONTRACTING INC. |
| TEL: 954-914-9848 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. NOV. 01/ 2017 |
| ACTION: DENIED |
| |
| 1) SHOP DRAWING SHEETS 1-5 (NOA# 17-0201.02) FROM |
| CHRISTOPHER STANTON P. E. ON SHEET 1 THE COVERSHEET |
| DOES HAVE A DIGITAL SIGNATURE THAT HAS BEEN PRINTED |
| OUT, CANNOT VERIFY A DIGITAL SIGNATURE WHEN IT IS |
| PRINTED. THIS SAME SHEET HAS A MINIATURIZED ENGINEER |
| SEAL OF 1 ? INCH IN DIAMETER AND COPIED SIGNATURE. |
| SHEETS 2-5 ONLY HAVE THE MINIATURIZED ENGINEER SEAL AND |
| COPIED SIGNATURE. NONE OF THE MINIATURIZED SEALS WITH |
| SIGNATURE ARE DATED. |
| |
| FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A |
| SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE |
| OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON |
| ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS, |
| SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| 61G15-23.001 ENGINEERS SEALS ACCEPTABLE TO THE BOARD. |
| SAID SEAL SHALL BE A MINIMUM OF 1 7/8 INCHES IN |
| DIAMETER, TO SAY LICENSE NOT CERTIFICATE. ALL ENGINEERS |
| MUST BE UTILIZING SAID SEAL NO LATER THAN JANUARY 1, |
| 2006. |
| |
| 2) THE SHOP DRAWING FOR NOA 14-1112.06) FROM |
| CHRISTOPHER STANTON P. E. ON SHEET 1 THE DOES HAVE A |
| DIGITAL SIGNATURE THAT HAS BEEN PRINTED OUT, CANNOT |
| VERIFY A DIGITAL SIGNATURE WHEN IT IS PRINTED. THIS |
| SAME SHEET HAS A MINIATURIZED ENGINEER SEAL OF 1 ? INCH |
| IN DIAMETER AND COPIED SIGNATURE, THE MINIATURIZED SEAL |
| WITH SIGNATURE IS NOT DATED. |
| |
| FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A |
| SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE |
| OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON |
| ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS, |
| SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| 61G15-23.001 ENGINEERS SEALS ACCEPTABLE TO THE BOARD. |
| SAID SEAL SHALL BE A MINIMUM OF 1 7/8 INCHES IN |
| DIAMETER, TO SAY LICENSE NOT CERTIFICATE. ALL ENGINEERS |
| MUST BE UTILIZING SAID SEAL NO LATER THAN JANUARY 1, |
| 2006. |
| |
| 3) THE ARCHITECT SHOP DRAWING STAMP OF APPROVAL FOR THE |
| NOA 17-0201.02 FROM PERKINS+ WILL IS NOT APPROVED, NO |
| EXCEPTIONS TAKEN. THE BOX CHECKED STATES FOR |
| INFORMATION ONLY. |
| W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 4) THE ARCHITECT PERKINS+ WILL DATED 07/31/2017 DOES |
| HAVE THE EXCEPTIONS AS NOTED BOX CHECKED BUT DOES NOT |
| IDENTIFY WHAT THEY HAVE APPROVED? 107.2.1.3 ADDITIONAL |
| INFORMATION IS REQUIRED. |
| |
| 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. |
| WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |