Date |
Text |
2017-11-08 08:20:55 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN |
| PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS |
| 471.003(2)(H); 471.025; FBC 107.2.1 |
| 2. WIRE FROM METER CAN TO SERVICE RATED TRANSFER SWITCH |
| IS REQUIRED TO BE SIZED FOR MAIN BREAKER IN TRANSFER |
| SWITCH. THE REDUCTIONS IN WIRE SIZE FROM 310.15(B)(7) |
| CANNOT BE USED FOR THIS BECAUSE THIS ALLOWANCE IS ONLY |
| FOR THE FEEDER THAT SUPPLIES 100% OF THE LOAD. SIZE |
| WIRE PER NEC 310.15(B)(16) AND PROVIDE CORRECTION. NEC |
| 310.15(B)(16); FBC RE TABLE E3603.1, 3704.1 |
| 3. WIRE FROM SERVICE RATED TRANSFER SWITCH TO PANEL IS |
| REQUIRED TO BE SIZED FOR MAIN BREAKER IN TRANSFER |
| SWITCH. THE REDUCTIONS IN WIRE SIZE FROM 310.15(B)(7) |
| CANNOT BE USED FOR THIS BECAUSE THIS ALLOWANCE IS ONLY |
| FOR THE FEEDER THAT SUPPLIES 100% OF THE LOAD. SIZE |
| WIRE PER NEC 310.15(B)(16) AND PROVIDE CORRECTION. NEC |
| 310.15(B)(16); FBC RE TABLE E3603.1, 3704.1 |
| 4. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| SERVICE. NEC 250.94; FBC RE3609.3 |
| 5. WIRES RUN IN PARALLEL FROM GENERATOR MUST BE A |
| MINUMUM SIZE OF 1/0 AWG. THIS CONDUIT MUST INCLUDE AN |
| EQUIPMENT GROUNDING CONDUCTOR. PROVIDE CORRECTION. NEC |
| 310.10(H)(1), 250.122; FBC RE 3704.6 |
| 6. PROVIDE SPEC SHEET FOR TRANSFER SWITCH. NEC 110.3; |
| FBC 107.2.1 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |