Plan Review Notes
Plan Review Notes For Permit 17101189
Permit Number 17101189
Review Stop E
Sequence Number 1
Notes
Date Text
2017-11-08 08:20:55CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS
 471.003(2)(H); 471.025; FBC 107.2.1
 2. WIRE FROM METER CAN TO SERVICE RATED TRANSFER SWITCH
 IS REQUIRED TO BE SIZED FOR MAIN BREAKER IN TRANSFER
 SWITCH. THE REDUCTIONS IN WIRE SIZE FROM 310.15(B)(7)
 CANNOT BE USED FOR THIS BECAUSE THIS ALLOWANCE IS ONLY
 FOR THE FEEDER THAT SUPPLIES 100% OF THE LOAD. SIZE
 WIRE PER NEC 310.15(B)(16) AND PROVIDE CORRECTION. NEC
 310.15(B)(16); FBC RE TABLE E3603.1, 3704.1
 3. WIRE FROM SERVICE RATED TRANSFER SWITCH TO PANEL IS
 REQUIRED TO BE SIZED FOR MAIN BREAKER IN TRANSFER
 SWITCH. THE REDUCTIONS IN WIRE SIZE FROM 310.15(B)(7)
 CANNOT BE USED FOR THIS BECAUSE THIS ALLOWANCE IS ONLY
 FOR THE FEEDER THAT SUPPLIES 100% OF THE LOAD. SIZE
 WIRE PER NEC 310.15(B)(16) AND PROVIDE CORRECTION. NEC
 310.15(B)(16); FBC RE TABLE E3603.1, 3704.1
 4. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94; FBC RE3609.3
 5. WIRES RUN IN PARALLEL FROM GENERATOR MUST BE A
 MINUMUM SIZE OF 1/0 AWG. THIS CONDUIT MUST INCLUDE AN
 EQUIPMENT GROUNDING CONDUCTOR. PROVIDE CORRECTION. NEC
 310.10(H)(1), 250.122; FBC RE 3704.6
 6. PROVIDE SPEC SHEET FOR TRANSFER SWITCH. NEC 110.3;
 FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  