2017-11-03 14:24:28 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17101137 | | PHILLIPS POINTE EAST TOWER | | 11/3/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) M0.1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW | | GREENHECK 48 MODEL RGU UPBLAST FAN, AND REFER TO 513 | | SMOKE CONTROL SYSTEMS, AND SPECIFICALLY SECTIONS | | 513.10, AND 513.10.5. VERIFY THAT THE NEW GREENHECK FAN | | IS RATED AND CERTIFIED BY THE MANUFACTURER FOR THE | | PROBABLE TEMPERATURE RISE, IS UL LISTED AS A POWER | | VENTILATOR FOR SMOKE CONTROL, AND THAT IT IS EQUIPPED | | WITH TWO BELTS (IF THE FAN IS BELT DRIVEN AND NOT | | DIRECT-DRIVE) | | | | 2) SHEET M3.1) PROVIDE THE WIND LOAD DESIGN CRITERIA | | PER SECTION 1609 FBC-14 BUILDING. | | | | 3) M4.1) THE SHEET TOO FAINT TO READ AND NOT LEGIBLE- | | SECTION 107.1 WPB AMENDMENTS TO THE FBC. | | | | 4) VERIFY THE FAN IS BEING SUPPLIED WITH TWO SOURCES OF | | POWER- PRIMARY FROM THE NORMAL BUILDING SYSTEM, AND | | SECONDARY FROM AN APPROVED STANDBY SOURCE- SECTION | | 513.11. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|