2017-11-03 14:24:281ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17101137
 PHILLIPS POINTE EAST TOWER
 11/3/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M0.1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW
 GREENHECK 48 MODEL RGU UPBLAST FAN, AND REFER TO 513
 SMOKE CONTROL SYSTEMS, AND SPECIFICALLY SECTIONS
 513.10, AND 513.10.5. VERIFY THAT THE NEW GREENHECK FAN
 IS RATED AND CERTIFIED BY THE MANUFACTURER FOR THE
 PROBABLE TEMPERATURE RISE, IS UL LISTED AS A POWER
 VENTILATOR FOR SMOKE CONTROL, AND THAT IT IS EQUIPPED
 WITH TWO BELTS (IF THE FAN IS BELT DRIVEN AND NOT
 DIRECT-DRIVE)
  
 2) SHEET M3.1) PROVIDE THE WIND LOAD DESIGN CRITERIA
 PER SECTION 1609 FBC-14 BUILDING.
  
 3) M4.1) THE SHEET TOO FAINT TO READ AND NOT LEGIBLE-
 SECTION 107.1 WPB AMENDMENTS TO THE FBC.
  
 4) VERIFY THE FAN IS BEING SUPPLIED WITH TWO SOURCES OF
 POWER- PRIMARY FROM THE NORMAL BUILDING SYSTEM, AND
 SECONDARY FROM AN APPROVED STANDBY SOURCE- SECTION
 513.11.
  