Plan Review Notes
Plan Review Notes For Permit 17101134
Permit Number 17101134
Review Stop M
Sequence Number 1
Notes
Date Text
2017-11-03 12:10:121ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17101134
 11/3/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO 513 SMOKE CONTROL SYSTEMS, AND SPECIFICALLY
 SECTIONS 513.10, AND 513.10.5. VERIFY THAT THE NEW
 GREENHECK TFI-FS FAN IS RATED AND CERTIFIED BY THE
 MANUFACTURER FOR THE PROBABLE TEMPERATURE RISE, IS UL
 LISTED AS A POWER VENTILATOR FOR SMOKE CONTROL, AND
 THAT IT IS EQUIPPED WITH TWO BELTS.
  
 2) SHEET M3.1) PROVIDE THE WIND LOAD DESIGN CRITERIA
 PER SECTION 1609 FBC-14 BUILDING.
  
 3) M4.1) THE SHEET IS TOO FAINT TO READ AND NOT
 LEGIBLE- SECTION 107.1 WPB AMENDMENTS TO THE FBC.
  
 4) VERIFY THE FAN IS BEING SUPPLIED WITH TWO SOURCES OF
 POWER- PRIMARY FROM THE NORMAL BUILDING SYSTEM, AND
 SECONDARY FROM AN APPROVED STANDBY SOURCE- SECTION
 513.11.
  