2018-01-18 09:04:482ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17101112
 1/18/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: IT IS ACKNOWLEDGED THAT THE REQUIRED
 SOURCE CAPTURE SYSTEMS FOR THE MANICURE AND PEDICURE
 STATIONS HAS BEEN PROVIDED, HOWEVER THE REQUIRED BEAUTY
 SALON EXHAUST VENTILATION SYSTEM HAS NOT BEEN PROVIDED
 AS WAS PREVIOUSLY REQUESTED- SEE TABLE 403.3. PLEASE
 NOTE THE FOLLOWING: THERE ARE TWO OUTSIDE AIR
 CALCULATION TABLES ON M-1. THE NEW TABLE ACCURATELY
  
 INDICATES 0.60 CFMS OF EXHAUST AIR REQUIRED FOR THE
 BEAUTY SALON AND SKIN CARE AREAS, HOWEVER THE OTHER
 TABLE INCCURATELY SPECIFIES AN OUTSIDE AIR (FRESH AIR)
 RATE OF 0.60 CFMS FOR OCCUPANTS. PLEASE CORRECT THIS
 CONFLICT AND PROVIDE THE SALON EXHAUST SYSTEM.
  
 2) M-1: DUCT SMOKE DETECTORS ARE REQUIRED IN THE RETURN
 AIR SYSTEMS OF AHU-1 & 2- SECTION 606.2.1.
  
 3) ADVISORY: APPROVED SHOP DRAWINGS FOR THE CHILLED
 WATER SUPPLY AND RETUN PIPING SHALL BE ONSITE AT TIME
 OF INSPECTION.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  