2018-01-22 15:59:39 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| COMMENTS WILL FOLLOW PREVIOUS COMMENTS. |
| 1. CORRECTED. |
| 2. CORRECTED. |
| 3. CORRECTED. |
| 4. CORRECTED. |
| 5. PROVIDE ACCURATE LOAD CALCULATION. THE PROVIDED |
| CALCULATION IS PERMITTED FOR A RESIDENCE ONLY, NOT FOR |
| COMMERCIAL BUILDINGS. PROVIDE CORRECTION. NEC 220; FBC |
| 107.2.1 (SEE NEW COMMENTS BELOW FOR ADDITIONAL |
| INFORMATION. IS THIS A PHASE SERVICE, OR SINGLE PHASE? |
| WHERE IS THE LOAD FOR MECHANICAL EQUIPMENT, IT IS NOT |
| SHOWN IN PANEL A? PROVIDE CORRECTIONS AND CORRECT |
| DISCREPANCIES.) |
| 6. CORRECTED. |
| 7. CORRECTED. |
| 8. CORRECTED. |
| 9. CORRECTED. |
| |
| NEW COMMENTS: |
| 10. THE ORIGINAL PLAN SUBMITTED SHOWED A SINGLE PHASE |
| SERVICE TO PANEL A. THE PLAN NOW SHOWS A 3 PHASE PANEL, |
| AND THE CORRESPONDING CALCULATIONS USING 3 PHASE |
| NUMBERS. HOWEVER, THE WIRE FEEDING THIS PANEL IS SHOWN |
| WITH THREE 4/0 CONDUCTORS AND A #6 EQUIPMENT GROUNDING |
| CONDUCTOR, WHICH IS SINGLE PHASE WIRING. IS THIS PANEL |
| AND THE SERVICE FEEDING IT SINGLE PHASE OR THREE PHASE? |
| PROVIDE CLARIFICATION AND CORRECTIONS AS NEEDED. FBC |
| 107.2.1 |
| 11. THERE IS NO MECHANICAL EQUIPMENT IN THE LOAD |
| CALCULATIONS BASED ON PANEL A. WHERE IS THIS EQUIPMENT |
| FED FROM? PROVIDE PANEL SCHEDULE AND LOAD CALCULATION |
| FOR THE PANEL FEEDING THIS EQUIPMENT TO VERIFY PROPER |
| SIZE. NEC 215.2, 215.5, 220, 408.4, 408.30; FBC 107.2.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |