Plan Review Notes For Permit 17101112
Permit Number 17101112
Review Stop E
Sequence Number 2
Notes
Date Text
2018-01-22 15:59:39CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL FOLLOW PREVIOUS COMMENTS.
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. PROVIDE ACCURATE LOAD CALCULATION. THE PROVIDED
 CALCULATION IS PERMITTED FOR A RESIDENCE ONLY, NOT FOR
 COMMERCIAL BUILDINGS. PROVIDE CORRECTION. NEC 220; FBC
 107.2.1 (SEE NEW COMMENTS BELOW FOR ADDITIONAL
 INFORMATION. IS THIS A PHASE SERVICE, OR SINGLE PHASE?
 WHERE IS THE LOAD FOR MECHANICAL EQUIPMENT, IT IS NOT
 SHOWN IN PANEL A? PROVIDE CORRECTIONS AND CORRECT
 DISCREPANCIES.)
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
 9. CORRECTED.
  
 NEW COMMENTS:
 10. THE ORIGINAL PLAN SUBMITTED SHOWED A SINGLE PHASE
 SERVICE TO PANEL A. THE PLAN NOW SHOWS A 3 PHASE PANEL,
 AND THE CORRESPONDING CALCULATIONS USING 3 PHASE
 NUMBERS. HOWEVER, THE WIRE FEEDING THIS PANEL IS SHOWN
 WITH THREE 4/0 CONDUCTORS AND A #6 EQUIPMENT GROUNDING
 CONDUCTOR, WHICH IS SINGLE PHASE WIRING. IS THIS PANEL
 AND THE SERVICE FEEDING IT SINGLE PHASE OR THREE PHASE?
 PROVIDE CLARIFICATION AND CORRECTIONS AS NEEDED. FBC
 107.2.1
 11. THERE IS NO MECHANICAL EQUIPMENT IN THE LOAD
 CALCULATIONS BASED ON PANEL A. WHERE IS THIS EQUIPMENT
 FED FROM? PROVIDE PANEL SCHEDULE AND LOAD CALCULATION
 FOR THE PANEL FEEDING THIS EQUIPMENT TO VERIFY PROPER
 SIZE. NEC 215.2, 215.5, 220, 408.4, 408.30; FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER