Plan Review Notes
Plan Review Notes For Permit 17101112
Permit Number 17101112
Review Stop M
Sequence Number 1
Notes
Date Text
2017-11-08 09:42:191ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17101112
 11/8/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 PLEASE NOTE THAT BUILDING DEPARTMENT RECORDS INDICATE
 AN EXISTING PERMIT APPLICATION FOR A BEAUTY SALON IN
 THE SAME CU-2 TENANT SPACE- PERMIT APPLICATION AND
 PLANS FOR THE SALON UNDER #17020366 ARE STILL UNDER
 REVIEW. IF THE CURRENT APPLICATION AND PLANS ARE TO
 REPLACE THE PREVIOUS SUBMITTALS, THEN #17020366 MUST BE
 REVOKED. FOR FURTHER INFORMATION PLEASE CONTACT CHIEF
 PLANS
  
 EXAMINER SAMANTHA HILL AT [email protected] 561-805-6724.
  
 1) THE HVAC PLAN AND OUTSIDE AIR CALCULATIONS FOR THE
 SALON ARE NOT IN COMPLIANCE WITH THE VENTILATION
 REQUIREMENTS IN SECTION 403.2.1 ITEM #3, AND TABLE
 403.3: PLEASE REVIEW THE FOLLOWING LIST OF DEFICIENCIES
 AND CORRECT THE PLAN.
  
 A) THE BEAUTY SALON REQUIRES AN EXHAUST SYSTEM WITH AN
 AIRFLOW RATE OF 0.60 CFMS PER SQ. FT. WHICH HAS NOT
 BEEN PROVIDED.
  
 B) RECIRCULATION OF AIR FROM THE BEAUTY SALON TO OTHER
 ROOMS AND SPACES IS PROHIBITED PER TABLE 403.3 FOOTNOTE
 B, THE CURRENT PLAN WHICH SHOWS AN OPEN PLENUM INSTEAD
 OF DUCTED RETURNS ALLOWS AIR FROM THE SALON TO BE
 RECIRCULATED TO THE SKIN CARE AND STAFF ROOMS.
  
 C) THE LOCATION OF THE NAIL EXHAUST INLET DOES NOT
 APPEAR TO BE CAPTURING THE FUMES AND ODORS AT THE
 SOURCES AS REQUIRED BY TABLE 403.3 FOOTNOTE H. PROVIDE
 ENLARGED DETAILS OF THE SYSTEMS AT THE MANICURE AND
 PEDICURE STATIONS TO VERIFY COMPLIANCE.
  
 D) THE OUTSIDE AIR CALCULATIONS ARE NOT IN COMPLIANCE
 WITH TABLE 403.3 WHICH REQUIRES AN OCCUPANT DENSITY OF
 25 PERSONS PER 1000 SQ. FT. WITH AN AIRFLOW RATE OF 20
 CFMS PER PERSON + 0.12 CFMS PER SQ. FT. PLEASE CORRECT
 THE CALCULATION.
  
 E) INDICATE THE TYPE OF O/A DUCTS TO BE INSTALLED, AND
 PROVIDE AUTOMATICALLY CONTROLLED SHUTOFF DAMPERS FOR
 THE DUCTS- SECTION C403.2.4.4 FBC-14 ENERGY
 CONSERVATION.
  
 F) PROVIDE AN AIR DEVICE SCHEDULE THAT LISTS THE MAKES
 AND MAKES OF THE DIFFUSERS AND GRILLS.
  
 2) SHEETS A-3 AND M-1: PLEASE INCLUDE THE W-6 MEZZANINE
 WALL IN THE LEGEND. IF THIS A FIRE-RATED WALL, FIRE
 DAMPERS SHALL BE PROVIDED FOR THE SUPPLY AND RETURN
 DUCTS PENETRATING IT.
  
 3) M-1: THE COMPLIANCE DATA FOR THE HEAT PUMPS
 INCLUDING THE EER AND THE COOLING CAPACITIES AS SHOWN
 IN THE SCHEDULE DO NOT MATCH THE DATA SHOWN IN THE
 COMCHECK COMPLIANCE CERTIFICATE.
  
 4) I AM CHALLENGING THE $58,400.00 VALUE LISTED ON THE
 APPLICATION IN ACCORDANCE WITH SECTION 109.3 WPB
 AMENDMENTS TO THE FBC. PLEASE PROVIDE A COPY OF A
 SIGNED CONTRACT FOR ALL PHASES OF THE PROJECT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  