2017-11-16 10:52:41 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. EXISTING GUTTER WIREWAY DOES NOT SHOW WIRE SIZES. |
| PROVIDE DETAILS FOR WIRE SIZE FEED AND OCP TO THIS |
| WIREWAY. NEC 215.2, 215.5, 240.4 |
| 2. PROVIDE LOAD CALCULATION FOR EXISTING GUTTER WIREWAY |
| TO DETERMINE THAT THE SERVICE IS ADEQUATE TO HANDLE THE |
| ADDITIONAL LOAD. NEC 220 |
| 3. PROVIDE AIC RATING OF SERVICE DISCONNECT. NEC 110.3, |
| 110.9 |
| 4. PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT |
| CURRENT AT DISCONNECT AND NEW PANEL TO CONFIRM AIC |
| RATING IS ADEQUATE. NEC 110.10 |
| 5. PROVIDE ACCURATE LOAD CALCULATION. THE PROVIDED |
| CALCULATION IS PERMITTED FOR A RESIDENCE ONLY, NOT FOR |
| COMMERCIAL BUILDINGS. PROVIDE CORRECTION. NEC 220; FBC |
| 107.2.1 |
| 6. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER |
| ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE |
| CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH |
| CODE. FBC CE 405.5 |
| 7. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED |
| IN THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE |
| AUTOMATIC CONTROL REQUIRED. FBC CE 405.2.2, 405.2.2.2 |
| 8. WILL THERE BE ANY SHOW WINDOWS? PROVIDE SHOW WINDOW |
| OUTLETS IF NECESSARY. NEC 210.62 |
| 9. PROVIDE GFCI PROTECTION FOR ANY OUTLETS WITHIN 6 |
| FEET OF WATER. EXAMPLES INCLUDE THE HAIR WASH, PEDICURE |
| CHAIR AND AREA, AND MANICURE AREAS. NEC 210.8 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |