Date |
Text |
2017-10-30 11:14:31 | ****PLAN REVIEW COMMENTS**** |
| |
| ART LANGE - BUILDING INSPECTOR |
| 561-805-6667 [email protected] |
| FBC FLORIDA BUILDING CODE 2014 5TH EDITION/ FRC FLORIDA |
| RESIDENTIAL CODE 2015 5TH EDITION |
| |
| 1. ENGINEERS INFORMATION ON TITLE BLOCK REQUIRED. |
| 61G1-16.004 TITLE BLOCK. |
| A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR |
| INTERIOR DESIGN DRAWINGS AND SPECIFICATION |
| IDENTIFICATION SHEETS THAT ARE REQUIRED TO BE SIGNED |
| AND SEALED. THE TITLE BLOCK MUST, AT A MINIMUM, CONTAIN |
| THE FOLLOWING INFORMATION: |
| (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. |
| (2) FIRM LICENSE NUMBER. |
| (3) NAME OR IDENTIFICATION OF PROJECT. |
| (4) DATE PREPARED. |
| (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. |
| (6) THE PRINTED NAME AND THE LICENSE/REGISTRATION |
| NUMBER OF THE PERSON SEALING THE DOCUMENT. |
| (7) THE DATE OF PLANS REVISION, IF THE PLANS ARE |
| REVISED. |
| (8) FOR THE PURPOSES OF THIS RULE, FIRM IS DEFINED TO |
| BE A CORPORATION, LIMITED LIABILITY COMPANY, |
| PARTNERSHIP, PERSON PRACTICING UNDER A FICTITIOUS NAME, |
| OR PERSON PRACTICING ARCHITECTURE OR INTERIOR DESIGN IN |
| HIS OR HER OWN NAME. |
| |
| 2. DETAIL ON A-2, PLASTIC PIPE THRU A SLEEVE IN 1HR |
| GYPSUM WALL. THIS DETAIL SHOWS WOOD FRAMING. WOOD |
| FRAMING NOT PERMITTED IN TYPE I CONSTRUCTION FBC 603. |
| |
| 3. SHOWER IN ROOM 1 IS SHOWN AS 36 X 30 FLOOR SPACE. |
| SEE FLORIDA ACCESSIBILITY CODE 608 FOR ACCEPTABLE |
| OPTIONAL SHOWER SIZE DETAILS. |
| |
| 4. STAFF ROOM #7 IS SHOWN AS 5? 7?. FBC 1208.1 MINIMUM |
| ROOM DIMENSION IS 7? . |
| |
| WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: |
| |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. |
| WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED |
| SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS |
| READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE |
| RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE |
| FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR |
| *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN |
| THE PERMIT PACKAGE. |
| A RESPONSE LETTER INDICATING HOW EACH ITEM WAS |
| ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. |
| |