1 |
|
Notes |
Date |
Text |
2017-11-27 14:51:27 | 1ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL | | PERMIT #17101099 | | 11/27/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET M1: THE AC EQUIPMENT SCHEDULE INDICATES THE | | 24000 BTUH (2-TON) AC SYSTEM WILL PRODUCE 6000 CFMS- | | PLEASE CORRECT. THE AVERAGE 2-TON SYSTEM PRODUCES | | APPROXIMATELY 800 CFMS. PLEASE NOTE THAT THE AC LAYOUT | | PLAN IS INDICATING 1150 TOTAL SUPPLY CFMS WHICH ALSO | | EXCEEDS THE CAPACITY OF THE SYSTEM, | | | | 2) PROVIDE CONDENSER TIE-DOWN DETAILS PER SECTIONS | | M1305.1.4.1 AND M1401.4. | | | | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE RANGE | | HOOD- SEE SECTION M1503.1. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|