Plan Review Notes
Plan Review Notes For Permit 17101099
Permit Number 17101099
Review Stop M
Sequence Number 1
Notes
Date Text
2017-11-27 14:51:271ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL
 PERMIT #17101099
 11/27/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1: THE AC EQUIPMENT SCHEDULE INDICATES THE
 24000 BTUH (2-TON) AC SYSTEM WILL PRODUCE 6000 CFMS-
 PLEASE CORRECT. THE AVERAGE 2-TON SYSTEM PRODUCES
 APPROXIMATELY 800 CFMS. PLEASE NOTE THAT THE AC LAYOUT
 PLAN IS INDICATING 1150 TOTAL SUPPLY CFMS WHICH ALSO
 EXCEEDS THE CAPACITY OF THE SYSTEM,
  
 2) PROVIDE CONDENSER TIE-DOWN DETAILS PER SECTIONS
 M1305.1.4.1 AND M1401.4.
  
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE RANGE
 HOOD- SEE SECTION M1503.1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER