2017-11-20 15:20:03CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ALL RECEPTACLES IN SHED ARE REQUIRED TO BE GFCI
 PROTECTED. PROVIDE CORRECTION. NEC 210.8; FBC RE 3902.2
 2. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR PANEL 3. NEC 225.31,
 225.32
 3. PROVIDE GROUNDING ELECTRODE SYSTEM AT SHED AS
 REQUIRED FOR A BUILDING OR STRUCTURE SUPPLIED BY A
 FEEDER OR BRANCH CIRCUIT. NEC 250.32; FBC RE3607.3
 4. PROVIDE ONE LOAD CALCULATION FOR ENTIRE SERVICE WITH
 ALL LOADS INCLUDED TO DETERMINE THAT THE SERVICE IS
 ADEQUATE. A SEPARATE LOAD CALCULATION FOR PANEL 2 IS
 PERMITTED FOR THE WIRE SIZE OF THE FEEDER TO THIS
 PANEL, HOWEVER, THE SAME TYPE OF CALCULATION IS NOT
 PERMITTED FOR PANEL 3. DEMAND FACTORS MAY ONLY BE USED
 WHEN THE FEEDER TO A PANEL IS 100 AMPS OR GREATER.
 PROVIDE FULL LOAD FOR PANEL 3 AND SIZE THE FEEDER WIRE
 AND OVERCURRENT PROTECTION ACCORDINGLY. FBC RE 3602.2;
 NEC 220.82(A)
 5. A CONFLICT EXIST IN THE NOTES ON PLAN. SEVERAL AREAS
 STATE THAT THE 2011 NEC SHOULD BE USED, BUT NOTE 5
 STATES THAT THE 2014 NEC SHOULD BE USED, WHICH IS NOT
 THE CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE
 6. SMOKE AND CO ALARMS SHOULD BE INSTALLED AT LEAST 3
 FEET FROM CEILING FANS OR MECHANICAL GRILLS. PROVIDE
 CORRECTION. NFPA 72, 29.8.3.6 AND .7.
 7. DINING ROOM CIRCUIT IS SHOWN FEEDING THE WALL
 OUTLETS AND LIGHTING WITH THE SAME CIRCUIT. DINING ROOM
 WALL OUTLETS CANNOT BE FED FROM A LIGHTING CIRCUIT.
 PROVIDE CORRECTION. NEC 210.52(B)(2); FBC RE 3703.2
 8. PANEL SCHEDULE FOR PANEL 2 SHOWS CIRCUIT 1 AS A # 12
 WIRE ON A 25 AMP BREAKER; CIRCUIT 19,21 AS A # 12 WIRE
 ON A 60 AMP BREAKER; CIRCUIT 8 AS A # 14 WIRE ON A 20
 AMP BREAKER. PROVIDE CORRECT WIRE AND/OR BREAKER SIZES
 FOR THE AMPACITY OF THE WIRE. NEC 310.15(B)(16); FBC RE
 3705.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER