Plan Review Notes
Plan Review Notes For Permit 17100958
Permit Number 17100958
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-10-26 12:34:31THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS INSUFFICIENT DETAIL PROVIDED TO CONDUCT AN
 ADAQUATE PLAN REVIEW.
  
  
 2) THE SUBMITTED PLAN DOES NOT INDICATE WHAT IS AN
 EXISTING, RELOCATED, NEW OR REMOVED SPRINKLER HEAD.
  
 PLEASE PROVIDE DETAILS.
  
  
 3) THE SUBMITTED PLANS DO NOT INDICATE WHAT IS AND WHAT
 SIZE IS AN EXISTING, RELOCATED, NEW OR REMOVED BRANCH
 LINE PIPING.
  
 PLEASE PROVIDE DETAILS.
  
  
 4) SIDEWALL SPRINKLERS ARE INDICATED, ARE THESE
 EXISTING AND/OR ARE THERE ANY OBSTRUCTIONS, INCLUDING
 BUT NOT LIMITED TO, CEILING FANS AND/OR LIGHT FIXTURES
 IN THESE ROOMS OR AREAS?
  
 PLEASE PROVIDE DETAILS.
  
  
 5) BASED ON ANY OF THE ABOVE, PLEASE INDICATE IF THE
 EXISITNG HYDRALIC CALCULATIONS WILL BE AFFECTED AND IF
 SO, PROVIDE REVISED CALCULATIONS.
  
 PLEASE PROVIDE DETAILS.
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  