2017-10-26 13:23:05 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| |
| THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| INSPECTION. |
| |
| |
| 1) ENSURE THAT THE CEILING FANS DO NOT CREATE |
| OBSTRUCTIONS FOR THE SIDEWALL SPRINKLERS. |
| |
| 8.7.5 OBSTRUCTIONS TO SPRINKLER DISCHARGE (STANDARD |
| SIDEWALL SPRAY SPRINKLERS). |
| 8.7.5.1.2 SIDEWALL SPRINKLERS SHALL BE INSTALLED NO |
| CLOSER THAN |
| 4 FT (1.2 M) FROM LIGHT FIXTURES OR SIMILAR |
| OBSTRUCTIONS. |
| 8.7.5.1.3 THE DISTANCE BETWEEN LIGHT FIXTURES OR |
| SIMILAR OBSTRUCTIONS |
| LOCATED MORE THAN 4 FT (1.2 M) FROM THE SPRINKLER SHALL |
| BE IN |
| CONFORMITY WITH TABLE 8.7.5.1.3 AND FIGURE 8.7.5.1.3. |
| |
| 8.9.5 OBSTRUCTIONS TO SPRINKLER DISCHARGE (EXTENDED |
| COVERAGE SIDEWALL SPRAY SPRINKLERS). |
| 8.9.5.1 PERFORMANCE OBJECTIVE. |
| 8.9.5.1.2 SIDEWALL SPRINKLERS SHALL BE INSTALLED NO |
| CLOSER THAN |
| 8 FT (2.4 M) FROM LIGHT FIXTURES OR SIMILAR |
| OBSTRUCTIONS. |
| 8.9.5.1.3 THE DISTANCE BETWEEN LIGHT FIXTURES OR |
| SIMILAR OBSTRUCTIONS |
| LOCATED MORE THAN 8 FT (2.4 M) FROM THE SPRINKLER SHALL |
| BE IN |
| CONFORMANCE WITH TABLE 8.9.5.1.3 AND FIGURE 8.9.5.1.3. |
| |
| |
| 2) INSPECTION TESTING. |
| |
| 1) TEST AT WORKING PRESSURE FOR 2 HOURS PER NFPA 13. |
| |
| 2) USE FIRE PUMP TEST PRESSURE FOR WORKING PRESSURE |
| CALCULATIONS. |
| |
| 3.3.19 SYSTEM WORKING PRESSURE. THE MAXIMUM ANTICIPATED |
| STATIC (NONFLOWING) OR FLOWING PRESSURE APPLIED TO |
| SPRINKLER SYSTEM COMPONENTS EXCLUSIVE OF SURGE |
| PRESSURES AND EXCLUSIVE OF PRESSURE FROM THE FIRE |
| DEPARTMENT CONNECTION. |
| |
| 24.2.1.2 PORTIONS OF SYSTEMS NORMALLY SUBJECTED TO |
| SYSTEM WORKING PRESSURES IN EXCESS OF 150 PSI (10.4 |
| BAR) SHALL BE TESTED AS DESCRIBED IN 24.2.1.1, AT A |
| PRESSURE OF 50 PSI (3.5 BAR) IN EXCESS OF SYSTEM |
| WORKING PRESSURE. |
| 24.2.1.4 MODIFICATIONS AFFECTING 20 OR FEWER SPRINKLERS |
| SHALL NOT REQUIRE TESTING IN EXCESS OF SYSTEM WORKING |
| PRESSURE. |
| 24.2.1.5 WHERE ADDITION OR MODIFICATION IS MADE TO AN |
| EXISTING SYSTEM AFFECTING MORE THAN 20 SPRINKLERS, THE |
| NEW PORTION SHALL BE ISOLATED AND TESTED AT NOT LESS |
| THAN 200 PSI (13.8 BAR) FOR 2 HOURS. |
| 24.2.1.6 MODIFICATIONS THAT CANNOT BE ISOLATED, SUCH AS |
| RELOCATED DROPS, SHALL NOT REQUIRE TESTING IN EXCESS OF |
| SYSTEM WORKING PRESSURE. |
| 24.2.1.7 LOSS SHALL BE DETERMINED BY A DROP IN GAUGE |
| PRESSURE OR VISUAL LEAKAGE. |
| 24.2.1.8* THE TEST PRESSURE SHALL BE READ FROM A GAUGE |
| LOCATED AT THE LOW ELEVATION POINT OF THE SYSTEM OR |
| PORTION BEING TESTED. THE PRESSURES IN PIPING AT HIGHER |
| ELEVATIONS SHALL BE PERMITTED TO BE LESS THAN 200 PSI |
| (13.8 BAR) WHEN ACCOUNTING FOR ELEVATION LOSSES. |
| SYSTEMS OR PORTIONS OF SYSTEMS THAT CAN BE ISOLATED |
| SHALL BE PERMITTED TO BE TESTED SEPARATELY. |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| |