Date Text
2017-10-26 13:23:05THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ENSURE THAT THE CEILING FANS DO NOT CREATE
 OBSTRUCTIONS FOR THE SIDEWALL SPRINKLERS.
  
 8.7.5 OBSTRUCTIONS TO SPRINKLER DISCHARGE (STANDARD
 SIDEWALL SPRAY SPRINKLERS).
 8.7.5.1.2 SIDEWALL SPRINKLERS SHALL BE INSTALLED NO
 CLOSER THAN
 4 FT (1.2 M) FROM LIGHT FIXTURES OR SIMILAR
 OBSTRUCTIONS.
 8.7.5.1.3 THE DISTANCE BETWEEN LIGHT FIXTURES OR
 SIMILAR OBSTRUCTIONS
 LOCATED MORE THAN 4 FT (1.2 M) FROM THE SPRINKLER SHALL
 BE IN
 CONFORMITY WITH TABLE 8.7.5.1.3 AND FIGURE 8.7.5.1.3.
  
 8.9.5 OBSTRUCTIONS TO SPRINKLER DISCHARGE (EXTENDED
 COVERAGE SIDEWALL SPRAY SPRINKLERS).
 8.9.5.1 PERFORMANCE OBJECTIVE.
 8.9.5.1.2 SIDEWALL SPRINKLERS SHALL BE INSTALLED NO
 CLOSER THAN
 8 FT (2.4 M) FROM LIGHT FIXTURES OR SIMILAR
 OBSTRUCTIONS.
 8.9.5.1.3 THE DISTANCE BETWEEN LIGHT FIXTURES OR
 SIMILAR OBSTRUCTIONS
 LOCATED MORE THAN 8 FT (2.4 M) FROM THE SPRINKLER SHALL
 BE IN
 CONFORMANCE WITH TABLE 8.9.5.1.3 AND FIGURE 8.9.5.1.3.
  
  
 2) INSPECTION TESTING.
  
 1) TEST AT WORKING PRESSURE FOR 2 HOURS PER NFPA 13.
  
 2) USE FIRE PUMP TEST PRESSURE FOR WORKING PRESSURE
 CALCULATIONS.
  
 3.3.19 SYSTEM WORKING PRESSURE. THE MAXIMUM ANTICIPATED
 STATIC (NONFLOWING) OR FLOWING PRESSURE APPLIED TO
 SPRINKLER SYSTEM COMPONENTS EXCLUSIVE OF SURGE
 PRESSURES AND EXCLUSIVE OF PRESSURE FROM THE FIRE
 DEPARTMENT CONNECTION.
  
 24.2.1.2 PORTIONS OF SYSTEMS NORMALLY SUBJECTED TO
 SYSTEM WORKING PRESSURES IN EXCESS OF 150 PSI (10.4
 BAR) SHALL BE TESTED AS DESCRIBED IN 24.2.1.1, AT A
 PRESSURE OF 50 PSI (3.5 BAR) IN EXCESS OF SYSTEM
 WORKING PRESSURE.
 24.2.1.4 MODIFICATIONS AFFECTING 20 OR FEWER SPRINKLERS
 SHALL NOT REQUIRE TESTING IN EXCESS OF SYSTEM WORKING
 PRESSURE.
 24.2.1.5 WHERE ADDITION OR MODIFICATION IS MADE TO AN
 EXISTING SYSTEM AFFECTING MORE THAN 20 SPRINKLERS, THE
 NEW PORTION SHALL BE ISOLATED AND TESTED AT NOT LESS
 THAN 200 PSI (13.8 BAR) FOR 2 HOURS.
 24.2.1.6 MODIFICATIONS THAT CANNOT BE ISOLATED, SUCH AS
 RELOCATED DROPS, SHALL NOT REQUIRE TESTING IN EXCESS OF
 SYSTEM WORKING PRESSURE.
 24.2.1.7 LOSS SHALL BE DETERMINED BY A DROP IN GAUGE
 PRESSURE OR VISUAL LEAKAGE.
 24.2.1.8* THE TEST PRESSURE SHALL BE READ FROM A GAUGE
 LOCATED AT THE LOW ELEVATION POINT OF THE SYSTEM OR
 PORTION BEING TESTED. THE PRESSURES IN PIPING AT HIGHER
 ELEVATIONS SHALL BE PERMITTED TO BE LESS THAN 200 PSI
 (13.8 BAR) WHEN ACCOUNTING FOR ELEVATION LOSSES.
 SYSTEMS OR PORTIONS OF SYSTEMS THAT CAN BE ISOLATED
 SHALL BE PERMITTED TO BE TESTED SEPARATELY.
  
 PETER LEDUC
 FIRE MARSHAL