Plan Review Notes For Permit 17100938 |
Permit Number |
17100938 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-11-15 09:34:39 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT #17100938 | | 11/15/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE DUCT DROP INTO THE NEW UTILITY ROOM IS NOT | | SHOWN- SEE THE AC CALCULATIONS WHICH CALL OUT A 5" DUCT | | SUPPLYING 84 CFMS OF COOLING AND 39 CFMS OF HEATING. | | | | 2) TWO SETS OF ENERGY AND AC CALCULATIONS MUST BE | | PROVIDED- ONLY ONE SET OF EACH WAS SUBMITTED- SECTTION | | 107.2.1 WPB AMENDMENTS TO THE FBC | | | | 2) 2ND REQUEST FOR SIGNATURE OF DESIGNER/CONTRACTOR ON | | PLAN. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | | | |
|