Plan Review Notes For Permit 17100938 |
Permit Number |
17100938 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-10-27 13:00:53 | 1ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL | | PERMIT #17100938 | | 10/27/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE NEW UTILITY ROOM IS DEFINED AS AN ADDITION | | ACCORDING TO SECTION R202 FBC-14 ENERGY CONSERVATION. | | PLEASE PROVIDE AN ENERGY COMPLIANCE SUBMITTAL USING | | EITHER THE THERMAL ENVELOPE ALTERNATIVE OR PERFORMANCE | | COMPLIANCE METHOD- SEE R101.5.1.1. | | | | 2) SUBMIT MANUFACTURER'S SPECIFCATIONS FOR THE GAS | | DRYER AND PROVIDE COMBUSTION AIR CALCULATIONS- SECTION | | G2407.1. FBC-14 RESIDENTIAL. | | | | 3) SIGNATURE OF CONTRACTOR OR QUALIFIER ON PLANS | | REQUIRED- SECTION 107.2.1 FBC. WPB AMENDMENTS TO THE | | FBC: ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|