2018-05-11 18:55:49PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 NOTE: THE FIRST REVIEW WAS DONE UNDER THE 2017 FBC DUE
 TO CLERICAL ERROR.
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATION. FBC
 ENERGY CONSERVATION - SECT. R403.7.1 EQUIPMENT SIZING.
 HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN
 ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT
 LOADS CALCULATED IN ACCORDANCE WITH MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES,
 BASED ON BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION
 OF THE BUILDING. THE MANUFACTURER AND MODEL NUMBER OF
 THE OUTDOOR AND INDOOR UNITS (IF SPLIT SYSTEM) SHALL BE
 SUBMITTED ALONG WITH THE SENSIBLE AND TOTAL COOLING
 CAPACITIES AT THE DESIGN CONDITIONS DESCRIBED IN
 SECTION 302.1. THIS CODE DOES NOT ALLOW DESIGNER SAFETY
 FACTORS, PROVISIONS FOR FUTURE EXPANSION OR OTHER
 FACTORS WHICH AFFECT EQUIPMENT SIZING. SYSTEM SIZING
 CALCULATIONS SHALL NOT INCLUDE LOADS CREATED BY LOCAL
 INTERMITTENT MECHANICAL VENTILATION SUCH AS STANDARD
 KITCHEN AND BATHROOM EXHAUST SYSTEMS. NEW OR
 REPLACEMENT HEATING AND COOLING EQUIPMENT SHALL HAVE AN
 EFFICIENCY RATING EQUAL TO OR GREATER THAN THE MINIMUM
 REQUIRED BY FEDERAL LAW FOR THE GEOGRAPHIC LOCATION
 WHERE THE EQUIPMENT IS INSTALLED.
 NEW COMMENT: THE EQUIPMENT SIZING CALCULATIONS AND
 ENERGY CODE COMPLIANCE FORMS THAT WERE SUBMITTED ARE ON
 THE 2017 FORMS. THIS PROJECT IS UNDER THE 2014 EDITION
 OF THE FBC.
  
 2) SUBMIT TWO SETS OF 2014 ENERGY CODE COMPLIANCE FORMS
 FOR THE NEW GARAGE, OFFICE AND GAME ROOM STRUCTURE. FBC
 ENERGY CONSERVATION - SECT. R103.1.1.2 CODE COMPLIANCE
 CERTIFICATION.
 NEW COMMENT: THE EQUIPMENT SIZING CALCULATIONS AND
 ENERGY CODE COMPLIANCE FORMS THAT WERE SUBMITTED ARE ON
 THE 2017 FORMS. THIS PROJECT IS UNDER THE 2014 EDITION
 OF THE FBC.
  
 3) NEW COMMENT: THE CODE COMPLIANCE FORMS ARE REQUIRED
 TO BE SIGNED BY THE OWNER/AGENT. FBC ENERGY
 CONSERVATION - SECT. R103.1.1.2
  
 4) NEW COMMENT: THE ENERGY CODE COMPLIANCE FORMS LIST 1
 BEDROOM AND THERE ARE NOT ANY BEDROOMS IN THIS
 STRUCTURE SHOWN ON THE PLANS. REVISE. FBC 107.2.1
  
 5) NEW COMMENT: THE EQUIPMENT SIZING CALULATIONS AND
 ENERGY FORMS DO NOT MATCH THE EQUIPMENT SCHEDULE ON THE
 PLANS. THE SIZING CALCULATIONS SPECIFY 2.2 TONS AND
 23,200 BTUH AND THE PLANS LIST 3 TONS AND 36,000 BTUH.
 PLEASE CORRECT FBC 107.2.1.