2018-04-02 17:43:52PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 NOTE: THE FIRST REVIEW WAS DONE UNDER THE 2017 FBC DUE
 TO CLERICAL ERROR.
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE RAS 117 CALCULATIONS THAT WERE SUBMITTED FOR NOA
 NO. 14-1030.02 ARE INCORRECT. THE FASTENER SPACINGS OF
 9 INCHES ON CENTER FOR ROOF ZONE 2 AND 6 INCHES O.C.
 FOR ROOF ZONE 3 ON THE BALCONY DO NOT MEET THE UPLIFTS
 FOR -65.9 PSF AND -109.1 PSF RESPECTIVELY. PLEASE
 CORRECT. FBC 107.2.1.3
  
 2) THE PRODUCT APPROVALS FOR NOA NO. 14-1003.02 WERE
 NOT SUBMITTED. BASED ON THE INFORMATION PROVIDED IN THE
 RAS 117 CALCULATIONS THAT WERE SUBMITTED FOR THAT NOA
 THE FASTENER SPACINGS FOR ROOF ZONES 2 AND 3 ARE
 INCORRECT. PLEASE CORRECT AND SUBMIT THE PRODUCT
 APPROVALS. FBC 107.2.1.3 & 107.3.4.1
  
 3) SUBMIT PLANS AND STRUCTURAL DETAILS FOR THE CORRIDOR
 FROM THE MAIN HOUSE TO THE TWO STORY GARAGE/GAME ROOM
 STRUCTURE. FBC 107.2.1